Note it is also still allowable to have circuits without RCD protection.
However one has to ensure that the cables are not liable to damage. That
means either burial at = 50mm or protection by earthed shielding of
some sort (e.g. metal conduit, or via a metal screened cable)
Or run the cables on the surface: AIUI it's only for cables buried 50mm
the RCD becomes necessary.
Yup, also true.
--
Cheers,
John.
/================================================== ===============\