"RBM" wrote in message
...

"Doug Miller" wrote in message
...
In the course of remodeling my bathroom, I just discovered that the
knucklehead who remodeled it the last time, some 25 or 30 years ago, made
a
splice inside the wall, behind the sink backsplash -- but not,
unfortunately,
in a junction box.

In the wall behind the sink cabinet are two stick-built medicine cabinets
with
mirrored doors that slide in tracks. Between the two is another large
mirror,
that also slides (although with some difficulty). There's sufficient
space
behind the central mirror to mount a proper junction box: see photo at
http://www.milmac.com/bathroom.jpg
showing what it looks like with the central mirror slid all the way to
the
left.

And it seems to me that doing so *does* comply with at least the *letter*
of the NEC requirements for accessibility, if not the spirit:

"Boxes ... shall be installed so that the wiring contained in them can be
rendered accessible without REMOVING any part of the building ..." [2005
and 2008 NEC, Art. 314.29 (emphasis added)]

Comments, please.


Looks easy to access to me. Certainly more easily accessible than the
junction boxes of some recessed fixtures




I concur with RBM.