On Apr 26, 10:29�pm, Robert Allison wrote:
James wrote:
Hmmmmmm......... i am not a contractor or much of a handyman, so this may be
silly, �but.........


Instead of thinking about cutting through 4 inches of concrete and laying
pvc pipe down, why can't you rent a concrete cutter and just cut a �1/2
inch �slit in the concrete, sufficient to lay down �UG wire (or whatever
would meet the code) into the slit ??


Any reason why this would not work ?


James


It would work, but it is not to code. �Any wiring (with the one
notable exception of grounding cable) in concrete must be in a
conduit.

--
Robert Allison
Rimshot, Inc.
Georgetown, TX


well a concrete saw cuts well, so use conduit.

its wierd when people need to go thru concrete they think it
impossible.......

with the proper tools its no biggie