Circuit Breaker Indication In A House Service Box Question
Robert11 wrote:
Hello:
Is it possible that when a circuit breaker in a service box opens due to a
short in the circuit that it is controlling, that the lever does not (also)
move to the other position ?
e.g., that there might not be any visible indication that it has tripped ?
If so, is this fairly common with circuit breakers in a house service box ?
Likely ?
Why ?
Thanks,
Bob
It all depends upon the mfr and the age of the device.
Some ancient ones were designed in a way that the handle
doesn't move to a "Tripped" position.
Some move all the way to Off; some to a center position.
Some must be moved to the full Off position before
they can be reset to On.
Jim
|