Earth bonding radiator in bathroom ?
"John Rumm" wrote in message
...
Ian_m wrote:
"ARWadworth" wrote in message
...
"Ian_m" wrote in message
...
The current radiator in my bathroom is earth bonded with 4mm2 wire, not
too sure why as all bathroom pipework is plastic (Osmagold) and there
are no electrics in bathroom.
So what is it bonded to? What is at the other end of the 4mm cable?
Goes back all the way to the earth bar in the CU. (in the CU there is a
wire labelled "bath rad").
Sounds like whoever installed it misunderstood the concept of
equipotential bonding as well then!
(the somewhat confused phrase "earth bonding" itself is partly the
problem - earthing and equipotential bonding are different things).
What a waste of time effort and money fitting this cable was. Feel free to
reomove it.
Adam
|