Default What is NEC Code For This Grounding Scheme ?

John Ross wrote:

bud-- wrote:
John Ross wrote:
This panel (there is only one at house) has NO ground bar--grounds and
neutrals are on the "neutral" bar. So he is proposing just adding
these new ground connections there as well. Is that OK? If they are
bonded together anyway, I can't see how it could hurt, but as you know
this is all new to me.

That is standard in service panels.

Are you saying it's standard to bond together in service panel


Bonding together is required. It is almost always done in the service panel.

or it's
common to just have the "neutral" bar and put grounds and neutrals on
it? I was thinking that they may have just made them like this all
those years ago, but now have the two bars in newer ones.


Just a neutral bar also used for grounds is common.

--
bud--