In article Gjzpi.4507$fJ5.1780@pd7urf1no, Tony Hwang wrote:
David Merrill wrote:
Attempting to connect two #14 ground wires to a single ground screw in
single-tube Lithonia fluoresecent fixtures joined end-to-end resulted in
stripping the screw threads in the sheet steel fixture. Is it acceptable to
substitute the next larger size of self-tapping machine screw. Of course it
won't be green and will be cadmium or zinc plated.
Alternatively, a longer ground might be screwed through a nut on the
backside of the fixture but this would be inconvenient.
David Merrill
Hi,
Of course.
You mean, of course NOT. Two wires under one screw is a Code violation except
where the terminals are specifically listed for multiple wires.
--
Regards,
Doug Miller (alphageek at milmac dot com)