In article , Bud-- wrote:
Doug Miller wrote:

This neutral wire is sharing the same screw terminal on the buss bar
with a ground wire from another circuit.


That is *not* OK unless the terminals are specifically listed for use with
more than one wire. If they are, it will say so on the label inside the panel
access door.

Neutrals must be 1 per terminal - 408.41.
[From an RBM post]

Didn't know that. Thanks.

--
Regards,
Doug Miller (alphageek at milmac dot com)