L1 to L2 around 80V
L1 to N - 127V
L2 to N - 11V


Assuming the voltages were measured with an electronic VOM I'd say that L2
is open between the breaker panel and the load. Most likely your
electrician cut or drilled through it.

Note that a 220/240V load doesn't care about the neutral; it only cares
about L1-L2.