Subpanel Grounding Question
On May 25, 8:56 am, Wayne Whitney wrote:
On 2007-05-25, wrote:
I already bought 10/3 UF and am going to start trenching and running
1" conduit in the morning.
Since you are using 10/3 UF are you going to be putting a 30 amp main
breaker in your 70 amp subpanel?
Cheers, Wayne
Good catch. I was focused on the grounding question. 10/3 would make
a pretty useless subpanel.
|