Default Electrical installation tubes


"Pygmalion" wrote in message
ps.com...

Pygmalion je napisal:
Conduits present in my flat are 18 mm internal diameter PVC tuboflex
conduits for concrete installation. They run all along flat, and they
are most probably connected at two places using usual insulating tape
(I guess this is not regular installing procedure). I tried to pull
one cable out of the conduit and I failed to move it out. Maybe I did
not use enough force.


I have just realised that conduits used for electric installations in
my flat are corrugated conduits.


Instead of pulling on the wire you should try pushing a fish tape through
the conduits and see how far it goes and where it goes to. If it comes out
some where, put a pull string on the end and pull it through. You can use
the pull string for pulling wire through in the future if you are not ready
to pull wire at that moment.