Default Sprinkler valve solenoid amps?

CRaSH wrote:
Dallas wrote:

Thanks to all that replied.

Yes, testing the voltage across the circuit with the solinoid
connected destroyed the voltage (near zero).

We finally found a damaged point in the underground wire where all the
current was leaking off into the ground.



It wasn't leaking off into ground, there just wasn't a good path for any
appreciable amount to be drawn by the solenoid.