A/C not starting up - Help needed
Radio Shack or Home Cheepo might have a suitable transformer.
--
Christopher A. Young
You can't shout down a troll.
You have to starve them.
..
"Speedy Jim" wrote in message
. com...
Peter wrote:
No 24V (no low voltage) coming off the terminals....... . Would
it do any good to
remove the relay and transformer to ohm them out ??? Is there
anyway to obtain
a replacement part ???
See if there is 120V on the xfmr primary. If there is, Ohm out
the primary. The relay shouldn't be needed just to get 24V from the
xfmr. If no 120V on primary, work back.
A tel. xfmr won't have enough voltage. Big Box store might have
HVAC basic components like this.
Jim
|