Jeff,

My incoming is barely warm to the touch.

And at 40% humidity, my system does not "stream" water out of it, more
like a rapid drip.
thank you very much for the thoughts! =)
Jeff wrote:
For a point of reference. My AC drops the inside air from 80 to 60 (outside
it was 84), there is a steady stream of water coming from the system. My
system works fine. Too high a delta T is inefficient, too low gives poor
dehumidification. Note the incoming Freon line (smaller line) is barely
warm to the touch. If your system is not similar to this something is
amiss. If it is then it may be too small for your home.