PVC Conduit Fill Rating?
wrote:
On 19 Jun 2006 13:28:36 -0700, "pbs" wrote:
Hi:
Can #12 THHN be run through 1' gray PVC Electrical conduit?
If Yes, what is the code fill rate for 1" PVC? ( I believe that 1" EMT
can handle 18 #12 THHN maximum.)
Thanks
Table C10 says 25 #12 THHN will fit is 1" sch 40 PVC rigid nonmetalic
conduit
Thanks. I had also intended to ask if the PVC conduit is permitted for
interior residential applications (this would run up through a chase)
|