A quick question - must the PRV on a sealed CH system be vented
outside?


Yes.

I would've thought so, however the surveyor made no mention of
it on a friend's survey (a full Building Survey I believe) so either he
missed it or is not obliged to check such things?


I would not expect a surveyor to know this, although some might.

As it currently stands the PRV would empty onto the kitchen floor in an
over-pressure condition.


You need to get that fixed. In a worse case failure condition,
that might be ejecting 40kW of steam, and that could seriously
injure or even kill someone in the kitchen.

--