Default RCD TRIPS ON MOST CIRCUITS ON NEW SPLIT LOAD CONSUMER UNIT

In article .com,
KevCompton wrote:
I had four circuits attached to the RCD - Downstairs sockets, upstairs
sockets, garage sockets and the Shower. All of the circuits trip the
RCD apart from the shower. I have temporarily moved these problem
circuits over to the non-rcd side and they are all working fine.


Are you *absolutely* sure both neutrals on the rings go to the correct
neutral busbar? It would be unusual to have so many faults.

--