KevCompton wrote:

Any ideas on possible causes and how to resolve this problem greatly
appreciated.


The usual problem is wiring the neutral of the RCD protected circuits
back to the non RCD protected neutral bus bar, rather than the dedicated
bus bar for RCD neutrals.

--
Cheers,

John.

/================================================== ===============\