Whats stoppping an upstream flow if the cylinder return is first by the
boiler?
Nothing. Either the cylinder should return after the radiators or the
radiators returns should join together before joining with the cylinder
return.
If the return pipework is not easy to modify then zoning the two sets of
the radiators (if that's a reasonable idea) would also fix the problem.
--
Ed Sirett - Property maintainer and registered gas fitter.