HW cylinder -- surprising numbers
Now that my heating controller is nearly done I've been using it to collect
data. Some of it is quite surprising, at least to me.
We have a ~25 year old 120L HW cylinder with foam insulation. Over a period
of 6 hours with no heat input (and just a couple of handwashes) the
temperature dropped from 61.5 C to 56.5 C. Measurements have a resolution of
0.1C. According to my calculations that represents a loss of ~2.5
megajoules, which over 6 hours is an average of ~115W.
I daresay modern cylinders could do a lot better than this, but somehow I
was expecting the losses to be higher.
Steve S
--
|