Dave, Could you expand a bit more on what you mean by "unbalances the
line and neutral." please?


In the UK, neutral is connected to earth at some point - the last possible
one being at the incoming main. After that, they are separate. Use the
earth cable in the house as a return and you are now not drawing equal
current on line and neutral. And RCDs work by looking for a difference in
the current flow between line and neutral, so you don't want to impose a
load which does just that. Of course, if it's only a couple of milliamps
it's unlikely to matter, but in principle it's a bad idea.

--