John M April 17th 04 02:58 PM

Radiator positioning
 
I have a 3 storey house and the toilet on the ground floor is the only room
without a radiator. There is no way to connect onto the central heating
pipes on the ground floor so I will have to run two pipes down the pipe
chase from the first floor. I know I will need to attach a drain point to
this part of the system as the main drain point would not empty the water in
this radiator. Can anyone forsee any problems with me attaching a radiator
in this way?

John



Set Square April 17th 04 03:54 PM

Radiator positioning
 
In an earlier contribution to this discussion,
John M wrote:

I have a 3 storey house and the toilet on the ground floor is the
only room without a radiator. There is no way to connect onto the
central heating pipes on the ground floor so I will have to run two
pipes down the pipe chase from the first floor. I know I will need to
attach a drain point to this part of the system as the main drain
point would not empty the water in this radiator. Can anyone forsee
any problems with me attaching a radiator in this way?

John


No problem. All my downstrairs rads are connected this way. Although my
house is only 2 storeys, the ground floor has solid floors - so no space for
underfloor pipes. The heating is distributed between the floors, with a pair
of pipes dropping down to each rad - each with a drain point, of course.
--
Cheers,
Set Square