asalcedo January 14th 19 10:30 PM

Air lock ?
 
After several months away I find that there is no cold water in my shower.

The hot water is fine.

The shower has a thermostatic mixer. When I open the water, only hot water comes out.

The shower is fed with a Stuart Turner Monsoon pump. Which, in turn, is fed via 22 mm copper pipes from the tanks in the loft.

The pump works fine with the hot water. With the cold water, since there is none, it does not pump any.

I seems like an air lock. Thus, I have removed the mixer and fed the cold water pipe on the wall with water with mains pressure (about 2.5 bar) via a garden hose connected to a tap nearby.

After several minutes, there is still no cold water flowing.

All the valves of the cold water pipes are open (as they were before).

Is there a non-return valve in the pump?

What else can I do to fix this?




Thanks,

Antonio

% January 14th 19 10:46 PM

Air lock ?
 
On 2019-01-14 3:30 p.m., asalcedo wrote:
After several months away I find that there is no cold water in my
shower.

The hot water is fine.

The shower has a thermostatic mixer. When I open the water, only hot
water comes out.

The shower is fed with a Stuart Turner Monsoon pump. Which, in turn, is
fed via 22 mm copper pipes from the tanks in the loft.

The pump works fine with the hot water. With the cold water, since there
is none, it does not pump any.

I seems like an air lock. Thus, I have removed the mixer and fed the
cold water pipe on the wall with water with mains pressure (about 2.5
bar) via a garden hose connected to a tap nearby.

After several minutes, there is still no cold water flowing.

All the valves of the cold water pipes are open (as they were before).

Is there a non-return valve in the pump?

What else can I do to fix this?




Thanks,

Antonio




did you run the hot water long enough to empty the hot water tank ,
you might not be getting any water at all except what's stored in the
hot water tank

asalcedo January 14th 19 11:13 PM

I did not run the hot water for very long. Plus it still keeps flowing well and hot from the hot shower pipe and from all the other hot water taps in the house. Plus the hot water tank is fed with mains water via the tank in the loft and the mains supply is fine and there is cold water in all other cold water taps in the house

Fredxx[_3_] January 14th 19 11:58 PM

Air lock ?
 
On 14/01/2019 22:30, asalcedo wrote:
After several months away I find that there is no cold water in my
shower.

The hot water is fine.

The shower has a thermostatic mixer. When I open the water, only hot
water comes out.

The shower is fed with a Stuart Turner Monsoon pump. Which, in turn, is
fed via 22 mm copper pipes from the tanks in the loft.

The pump works fine with the hot water. With the cold water, since there
is none, it does not pump any.

I seems like an air lock. Thus, I have removed the mixer and fed the
cold water pipe on the wall with water with mains pressure (about 2.5
bar) via a garden hose connected to a tap nearby.

After several minutes, there is still no cold water flowing.

All the valves of the cold water pipes are open (as they were before).

Is there a non-return valve in the pump?

What else can I do to fix this?


Where does the cold feed come from? Does it come from a tank, and is it
pumped like the hot?

Jim GM4DHJ ... January 15th 19 07:20 AM

Air lock ?
 

"asalcedo" wrote in message
...

After several months away I find that there is no cold water in my
shower.

The hot water is fine.

The shower has a thermostatic mixer. When I open the water, only hot
water comes out.

The shower is fed with a Stuart Turner Monsoon pump. Which, in turn, is
fed via 22 mm copper pipes from the tanks in the loft.

The pump works fine with the hot water. With the cold water, since there
is none, it does not pump any.

I seems like an air lock. Thus, I have removed the mixer and fed the
cold water pipe on the wall with water with mains pressure (about 2.5
bar) via a garden hose connected to a tap nearby.

After several minutes, there is still no cold water flowing.

All the valves of the cold water pipes are open (as they were before).

Is there a non-return valve in the pump?

What else can I do to fix this?


I found at the static caraven that the hot and cold feeds to the
thermostatic mixer were around the wrong way and I only got hot ......



asalcedo January 15th 19 08:35 AM

Where does the cold feed come from? Does it come from a tank, and is it
pumped like the hot?[/quote]

The cold feed comes from a tank in the loft, about three meters higher. The cold water is pumped with the same pump as the hot

Brian Gaff January 15th 19 09:07 AM

Air lock ?
 
So is this your home shower? How come you do not know if the cold is
pumped?
Id suggest either the pump is stuck or not working. Its probably time to
track the route of the cold feed and see what you find.
Brian

--
----- --
This newsgroup posting comes to you directly from...
The Sofa of Brian Gaff...

Blind user, so no pictures please
Note this Signature is meaningless.!
"Fredxx" wrote in message
...
On 14/01/2019 22:30, asalcedo wrote:
After several months away I find that there is no cold water in my
shower.

The hot water is fine.

The shower has a thermostatic mixer. When I open the water, only hot
water comes out.

The shower is fed with a Stuart Turner Monsoon pump. Which, in turn, is
fed via 22 mm copper pipes from the tanks in the loft.

The pump works fine with the hot water. With the cold water, since there
is none, it does not pump any.

I seems like an air lock. Thus, I have removed the mixer and fed the
cold water pipe on the wall with water with mains pressure (about 2.5
bar) via a garden hose connected to a tap nearby.

After several minutes, there is still no cold water flowing.

All the valves of the cold water pipes are open (as they were before).

Is there a non-return valve in the pump?

What else can I do to fix this?


Where does the cold feed come from? Does it come from a tank, and is it
pumped like the hot?




harry January 15th 19 09:51 AM

Air lock ?
 
On Monday, 14 January 2019 22:39:22 UTC, asalcedo wrote:
After several months away I find that there is no cold water in my
shower.

The hot water is fine.

The shower has a thermostatic mixer. When I open the water, only hot
water comes out.

The shower is fed with a Stuart Turner Monsoon pump. Which, in turn, is
fed via 22 mm copper pipes from the tanks in the loft.

The pump works fine with the hot water. With the cold water, since there
is none, it does not pump any.

I seems like an air lock. Thus, I have removed the mixer and fed the
cold water pipe on the wall with water with mains pressure (about 2.5
bar) via a garden hose connected to a tap nearby.

After several minutes, there is still no cold water flowing.

All the valves of the cold water pipes are open (as they were before).

Is there a non-return valve in the pump?

What else can I do to fix this?




Thanks,

Antonio



There may well be none return valves in both hot and cold water pipes, usually in the mixing valve body.
Try slackening off the connection to your pump and see if water is getting that far.
Also check that the pipe outlets from the cold water tank in the loft are not blocked with debris or dead bird/rodent. (Is the tank covered)?

asalcedo January 15th 19 01:04 PM

Quote:

Originally Posted by harry (Post 4228587)
Antonio
[/i][/color]


There may well be none return valves in both hot and cold water pipes, usually in the mixing valve body.
Try slackening off the connection to your pump and see if water is getting that far.
Also check that the pipe outlets from the cold water tank in the loft are not blocked with debris or dead bird/rodent. (Is the tank covered)?

This is becoming a tough one.

There are two non-return valves in the shower mixer, but the mixer is removed, so it does not affect.

Stuart Turner tech support says that this pump does not have any non-return valve. So, they say there must be a blockage somewhere else.

I have tried slackening off a bit the connection to the pump, and there is water in both the in and the out pipes. I cannot open it more because it would flood a delicate area. So I cannot tell if there is pressure there.

I have checked the tanks in the loft with a USB camera. I have confirmed that the entrances to the pipes coming out of the tanks are clean and clear of any obstruction. The tank is covered and there is no indication of debris or vermin.

I have tried again mains pressure at the end of the pipe in the shower. For about 5 minutes, then 5 minutes without pressure and then another few minutes under pressure. No difference. The connection to the shower pipe fitting is not perfect, there is some water spilling out, but still plenty of pressure is applied.

harry January 15th 19 06:35 PM

Air lock ?
 
On Tuesday, 15 January 2019 13:19:15 UTC, asalcedo wrote:
harry;4228587 Wrote:

Antonio



There may well be none return valves in both hot and cold water pipes,
usually in the mixing valve body.
Try slackening off the connection to your pump and see if water is
getting that far.
Also check that the pipe outlets from the cold water tank in the loft
are not blocked with debris or dead bird/rodent. (Is the tank covered)?


This is becoming a tough one.

There are two non-return valves in the shower mixer, but the mixer is
removed, so it does not affect.

Stuart Turner tech support says that this pump does not have any
non-return valve. So, they say there must be a blockage somewhere else.

I have tried slackening off a bit the connection to the pump, and there
is water in both the in and the out pipes. I cannot open it more
because it would flood a delicate area. So I cannot tell if there is
pressure there.

I have checked the tanks in the loft with a USB camera. I have confirmed
that the entrances to the pipes coming out of the tanks are clean and
clear of any obstruction. The tank is covered and there is no indication
of debris or vermin.

I have tried again mains pressure at the end of the pipe in the shower.
For about 5 minutes, then 5 minutes without pressure and then another
few minutes under pressure. No difference. The connection to the shower
pipe fitting is not perfect, there is some water spilling out, but still
plenty of pressure is applied.




--
asalcedo[/i][/color]

Well your mains pressure flush should clear it.
You need to be sure the mains water is actually getting through.
While the mains water is connected to to your cold water pipe, observe the water level in the roof tank & make sure it's rising so you are sure it's getting through.

asalcedo January 15th 19 08:11 PM

Problem solved.

A semi-stuck gate valve that a guest had closed...

Morale of the story, never assume anything, and gate valves can be difficult to read.

harry January 16th 19 09:06 AM

Air lock ?
 
On Tuesday, 15 January 2019 20:19:15 UTC, asalcedo wrote:
Problem solved.

A semi-stuck gate valve that a guest had closed...

Morale of the story, never assume anything, and gate valves can be
difficult to read.


Morale, always look for the simple things first!