Hi all,

I fitted a condensing boiler a few months ago, not in the same place as
the original floor-stander. Since then It's been working with a
temporary condensate drain running into the top of an unfinished soil
stack. Not particularly ideal, but it worked without any issues - not
even smells!

Now though I've got round to re-doing it "properly", which consisted of
installing an appliance standpipe directly underneath the boiler drain.
This has the side effect that the boiler now makes a piddling noise
which can be heard in the room above.

It probably won't be an issue once the whole lot is in a cupboard, but I
just wondered if there was an easy way to silence it. Any ideas?

Cheers,

Colin.
  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 14,085
Default How to stop the boiler piddling?

On Sat, 07 Dec 2013 23:07:22 +0000, Colin Stamp wrote:

Now though I've got round to re-doing it "properly", which consisted of
installing an appliance standpipe directly underneath the boiler drain.
This has the side effect that the boiler now makes a piddling noise
which can be heard in the room above.


Presumably the stand pipe has a trap and you can hear the condensate
dropping from the boiler drain into the water in the trap? If so just
arrange for the condensate to flow down the side of the stand pipe.
Maybe cut the end of the drain pipe at an angle and place the point
against the side of the standpipe.

--
Cheers
Dave.



  #3   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 214
Default How to stop the boiler piddling?

On 08/12/2013 09:46, Chris Hogg wrote:
On Sun, 08 Dec 2013 00:59:01 +0000 (GMT), "Dave Liquorice"
wrote:

On Sat, 07 Dec 2013 23:07:22 +0000, Colin Stamp wrote:

Now though I've got round to re-doing it "properly", which consisted of
installing an appliance standpipe directly underneath the boiler drain.
This has the side effect that the boiler now makes a piddling noise
which can be heard in the room above.


Presumably the stand pipe has a trap and you can hear the condensate
dropping from the boiler drain into the water in the trap? If so just
arrange for the condensate to flow down the side of the stand pipe.
Maybe cut the end of the drain pipe at an angle and place the point
against the side of the standpipe.


Failing that, tie one end of a bit of thick string around the boiler
drain pipe and push the other end into the top of the stand pipe, and
arrange it so that the condensate dribbles down the string.


I think I'll try getting the water to run down the side first. I think
what's making it worse is that it's already fallen the best part of a
metre inside the boiler drain pipe, so it's going quite fast when it exits.

The current plan is to glue an elbow onto the end of the boiler pipe,
facing the wall of the standpipe, and then cut it off flush. Then the
water should only fall a few cm before hitting the water in the trap.

Hopefully, piddling in the drain pipe should be more muffled than
piddling at the bottom of the standpipe...

Cheers,

Colin.
  #4   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 14,085
Default How to stop the boiler piddling?

On Sun, 08 Dec 2013 10:32:39 +0000, Colin Stamp wrote:

I think I'll try getting the water to run down the side first. I think
what's making it worse is that it's already fallen the best part of a
metre inside the boiler drain pipe, so it's going quite fast when it
exits.


That doesn't help but sort of surprised that the condensate isn't on
the side of the boiler drain pipe as it leaves the boiler. If it
isn't I'd look for some means of making it so. Maybe a disc a
diameter slightly more than the ID of a joint with a segment removed.
Inserted into the joint so that the cone formed is pointing up,
anything falling down the pipe above should then hit the cone flow to
the edges and out through the gap made by the missing segment,
against the pipe wall.

--
Cheers
Dave.



  #5   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 214
Default How to stop the boiler piddling?

On 08/12/2013 14:15, Dave Liquorice wrote:
On Sun, 08 Dec 2013 10:32:39 +0000, Colin Stamp wrote:

I think I'll try getting the water to run down the side first. I think
what's making it worse is that it's already fallen the best part of a
metre inside the boiler drain pipe, so it's going quite fast when it
exits.


That doesn't help but sort of surprised that the condensate isn't on
the side of the boiler drain pipe as it leaves the boiler. If it
isn't I'd look for some means of making it so. Maybe a disc a
diameter slightly more than the ID of a joint with a segment removed.
Inserted into the joint so that the cone formed is pointing up,
anything falling down the pipe above should then hit the cone flow to
the edges and out through the gap made by the missing segment,
against the pipe wall.


I think it probably does come down the wall of the boiler drain pipe.
The difficulty was getting it to transfer to the wall of the standpipe
rather than just shooting off the end of the drain pipe and free
falling the rest of the way. The boiler dumps quite a lot at a time. It
has a siphon thing to batch it up.

I've put the elbow on now and it's reduced the noise quite a bit. I
reckon it'll definitely be fine now once it's behind the false back of a
kitchen cupboard.

Cheers,

Colin.
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
combi boiler and solid fuel back boiler in tandem Phil L UK diy 2 December 4th 11 05:34 PM
outside stop cock doesn't stop water when turned. Clare UK diy 13 July 19th 09 06:37 PM
Saving Oil Installing Flue Mechanism to Stop Cold Air From Boiler? traderfjp Home Repair 2 September 26th 05 05:23 PM
Complicated central Heating; Back-Boiler and Combi-Boiler tfc715 UK diy 1 February 3rd 05 05:30 PM
DP depth stop / quill stop Gerald Ross Woodturning 3 December 28th 04 03:16 PM


All times are GMT +1. The time now is 08:35 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"