Colin Green June 6th 12 10:39 PM

Alternatives to downlighters in insulated flat roof .
 
Hi,

Looking for some alternative lighting solutions for a loft conversion.

- Loft conversion with large dormer with a flat roof.
- Flat roof is insulated with celotex [equivalent] between the joists and another 50mm fixed below the joists (so 150mm or so of celotext in total).


For lighting my initial instinct was to go with downlighters (spotlights) to make best use of the limited ceiling height, but having looked into it I'd much prefer to not to have large holes cut into the insulation (because of resulting poorer insulation, compromised moisture barrier, possible contravention of regs, etc.).

What lighting alternatives are available? I'm thinking maybe some kind of low profile light fittings around the edges of the ceilings, I figure if the light is cast across the ceiling then it will reflect off and illuminate the whole room reasonably well. I want to avoid having protruding light fittings (even low profile) in the centre of the ceilings as there is already limited headroom and therefore I think they would just be annoying.

Thoughts? (Links to actual fitting welcome!)

Colin.


Newshound June 6th 12 11:01 PM

Alternatives to downlighters in insulated flat roof .
 
On 06/06/2012 22:39, Colin Green wrote:
Hi,

Looking for some alternative lighting solutions for a loft conversion.

- Loft conversion with large dormer with a flat roof.
- Flat roof is insulated with celotex [equivalent] between the joists and another 50mm fixed below the joists (so 150mm or so of celotext in total).


For lighting my initial instinct was to go with downlighters (spotlights) to make best use of the limited ceiling height, but having looked into it I'd much prefer to not to have large holes cut into the insulation (because of resulting poorer insulation, compromised moisture barrier, possible contravention of regs, etc.).

What lighting alternatives are available? I'm thinking maybe some kind of low profile light fittings around the edges of the ceilings, I figure if the light is cast across the ceiling then it will reflect off and illuminate the whole room reasonably well. I want to avoid having protruding light fittings (even low profile) in the centre of the ceilings as there is already limited headroom and therefore I think they would just be annoying.

Thoughts? (Links to actual fitting welcome!)

Colin.


I have a living room with a low ceiling, and I light that using
uplighters on the walls. Standard Wickes ceramic ones, using CFLs.

NT[_2_] June 7th 12 12:08 AM

Alternatives to downlighters in insulated flat roof .
 
On Jun 6, 10:39*pm, Colin Green wrote:
Hi,

Looking for some alternative lighting solutions for a loft conversion.

*- Loft conversion with large dormer with a flat roof.
*- Flat roof is insulated with celotex [equivalent] between the joists and another 50mm fixed below the joists (so 150mm or so of celotext in total).

For lighting my initial instinct was to go with downlighters (spotlights) to make best use of the limited ceiling height, but having looked into it I'd much prefer to not to have large holes cut into the insulation (because of resulting poorer insulation, compromised moisture barrier, possible contravention of regs, etc.).

What lighting alternatives are available? I'm thinking maybe some kind of low profile light fittings around the edges of the ceilings, I figure if the light is cast across the ceiling then it will reflect off and illuminate the whole room reasonably well. I want to avoid having protruding light fittings (even low profile) in the centre of the ceilings as there is already limited headroom and therefore I think they would just be annoying.

Thoughts? (Links to actual fitting welcome!)

Colin.


Uplighters work well, but avoid the grim plaster things, they're just
a mistake. If headroom is low, its best to go with a many low power
uplighting, and/or wall lights. Or you can be bold about it and mount
a shallow trough inches under the ceiling down the full lenth of the
room and put heavily dimmed fl uplighting in it. 3500K is nice.


NT

harry June 7th 12 07:36 AM

Alternatives to downlighters in insulated flat roof .
 
On Jun 6, 10:39*pm, Colin Green wrote:
Hi,

Looking for some alternative lighting solutions for a loft conversion.

*- Loft conversion with large dormer with a flat roof.
*- Flat roof is insulated with celotex [equivalent] between the joists and another 50mm fixed below the joists (so 150mm or so of celotext in total).

For lighting my initial instinct was to go with downlighters (spotlights) to make best use of the limited ceiling height, but having looked into it I'd much prefer to not to have large holes cut into the insulation (because of resulting poorer insulation, compromised moisture barrier, possible contravention of regs, etc.).

What lighting alternatives are available? I'm thinking maybe some kind of low profile light fittings around the edges of the ceilings, I figure if the light is cast across the ceiling then it will reflect off and illuminate the whole room reasonably well. I want to avoid having protruding light fittings (even low profile) in the centre of the ceilings as there is already limited headroom and therefore I think they would just be annoying.

Thoughts? (Links to actual fitting welcome!)

Colin.


Wall lights/and plug-in bedside lights.

Tim Watts[_2_] June 7th 12 10:34 AM

Alternatives to downlighters in insulated flat roof .
 
Colin Green wrote:

Hi,

Looking for some alternative lighting solutions for a loft conversion.

- Loft conversion with large dormer with a flat roof.
- Flat roof is insulated with celotex [equivalent] between the joists and
another 50mm fixed below the joists (so 150mm or so of celotext in
total).


For lighting my initial instinct was to go with downlighters (spotlights)
to make best use of the limited ceiling height, but having looked into it
I'd much prefer to not to have large holes cut into the insulation
(because of resulting poorer insulation, compromised moisture barrier,
possible contravention of regs, etc.).

What lighting alternatives are available? I'm thinking maybe some kind of
low profile light fittings around the edges of the ceilings, I figure if
the light is cast across the ceiling then it will reflect off and
illuminate the whole room reasonably well. I want to avoid having
protruding light fittings (even low profile) in the centre of the ceilings
as there is already limited headroom and therefore I think they would just
be annoying.

Thoughts? (Links to actual fitting welcome!)

Colin.


http://www.mygreenlighting.co.uk/fur...cent/1590.html

I've used 6 for bay window lighting (2 per bay) with 13W lamps fitted.

Pros:
Cheap fitting
Low profile
Look smart
Good diffuse light with wide dispersion angle


Cons:
GX53 lamps - namely expensive and very slow start (2-3 mins to full
brightness because the tube is folded to buggery)

The cons are OK for me as these lights will tend to be on or off for long
periods rather than on/off for short periods. I'm hoping for a reasonable
lamp life.

There are a fair few LED GX53s coming which would solve the startup time but
will also be expensive.



These fittings can take the cable out the side or out the rear.


HTH

Tim

--
Tim Watts

sm_jamieson June 8th 12 09:36 AM

Alternatives to downlighters in insulated flat roof .
 
On Thursday, June 7, 2012 12:08:08 AM UTC+1, NT wrote:
On Jun 6, 10:39*pm, Colin Green wrote:
Hi,

Looking for some alternative lighting solutions for a loft conversion.

*- Loft conversion with large dormer with a flat roof.
*- Flat roof is insulated with celotex [equivalent] between the joists and another 50mm fixed below the joists (so 150mm or so of celotext in total).

For lighting my initial instinct was to go with downlighters (spotlights) to make best use of the limited ceiling height, but having looked into it I'd much prefer to not to have large holes cut into the insulation (because of resulting poorer insulation, compromised moisture barrier, possible contravention of regs, etc.).

What lighting alternatives are available? I'm thinking maybe some kind of low profile light fittings around the edges of the ceilings, I figure if the light is cast across the ceiling then it will reflect off and illuminate the whole room reasonably well. I want to avoid having protruding light fittings (even low profile) in the centre of the ceilings as there is already limited headroom and therefore I think they would just be annoying.

Thoughts? (Links to actual fitting welcome!)

Colin.


Uplighters work well, but avoid the grim plaster things, they're just
a mistake.


The quarter sphere things ?
I think they look good in hallways and landings, but nowhere else.
But they look tasteless when painted the same colour as the emulsion !
Simon.

Newshound June 8th 12 02:48 PM

Alternatives to downlighters in insulated flat roof .
 


Uplighters work well, but avoid the grim plaster things, they're just
a mistake.


The quarter sphere things ?
I think they look good in hallways and landings, but nowhere else.
But they look tasteless when painted the same colour as the emulsion !
Simon.


I reckon my grim plaster things look OK, emulsioned the same colour as
the walls. I've got oak beams, pine wainscotting, and exposed stone
above an inglenook to provide visual interest, the uplighters just blend
in. YMMV

Rick Hughes[_5_] June 8th 12 03:57 PM

Alternatives to downlighters in insulated flat roof .
 
On 06/06/2012 22:39, Colin Green wrote:
Hi,

Looking for some alternative lighting solutions for a loft conversion.

- Loft conversion with large dormer with a flat roof.
- Flat roof is insulated with celotex [equivalent] between the joists and another 50mm fixed below the joists (so 150mm or so of celotext in total).


For lighting my initial instinct was to go with downlighters (spotlights) to make best use of the limited ceiling height, but having looked into it I'd much prefer to not to have large holes cut into the insulation (because of resulting poorer insulation, compromised moisture barrier, possible contravention of regs, etc.).

What lighting alternatives are available? I'm thinking maybe some kind of low profile light fittings around the edges of the ceilings, I figure if the light is cast across the ceiling then it will reflect off and illuminate the whole room reasonably well. I want to avoid having protruding light fittings (even low profile) in the centre of the ceilings as there is already limited headroom and therefore I think they would just be annoying.

Thoughts? (Links to actual fitting welcome!)

Colin.

Uplighters

NT[_2_] June 8th 12 05:08 PM

Alternatives to downlighters in insulated flat roof .
 
On Jun 8, 2:48*pm, newshound wrote:
Uplighters work well, but avoid the grim plaster things, they're just
a mistake.


The quarter sphere things ?
I think they look good in hallways and landings, but nowhere else.
But they look tasteless when painted the same colour as the emulsion !
Simon.


I reckon my grim plaster things look OK, emulsioned the same colour as
the walls. I've got oak beams, pine wainscotting, and exposed stone
above an inglenook to provide visual interest, the uplighters just blend
in. YMMV


The bulbs are too close to the plaster. They show up the tiniest
imperfections on the wall, and create an intense light area. Decent
uplighting does neither


NT

Colin Green June 10th 12 11:04 PM

Alternatives to downlighters in insulated flat roof .
 
Thanks for the feedback.

I've gone for a few downlights where appropriate, e.g. two in a small bathroom (one is a combined spot/extractor vent) and three in a part of the roof where the above insulation is much deeper (and thus I don't mind so much about having holes cut into it). Everywhere else I have opted for lighting sockets adjacent to the normal 3 pin sockets, but they are switched via light switches positioned as you would normally expect them. I can plug various lights into these (e.g. floor and table lamps) and thus allow more flexible use of the already restricted space.

The electrician actually suggested this option and it's not something I was aware of as an option until he mentioned it. I'm not sure what the exact type of socket/plug he will be using is - anyone on here know what the standard is for this? (if any) (just so I'm happy this doesn't contravene any regs).

Thanks,

Colin




NT[_2_] June 10th 12 11:35 PM

Alternatives to downlighters in insulated flat roof .
 
On Jun 10, 11:04*pm, Colin Green wrote:
Thanks for the feedback.

I've gone for a few downlights where appropriate, e.g. two in a small bathroom (one is a combined spot/extractor vent) and three in a part of the roof where the above insulation is much deeper (and thus I don't mind so much about having holes cut into it). Everywhere else I have opted for lighting sockets adjacent to the normal 3 pin sockets, but they are switched via light switches positioned as you would normally expect them. I can plug various lights into these (e.g. floor and table lamps) and thus allow more flexible use of the already restricted space.

The electrician actually suggested this option and it's not something I was aware of as an option until he mentioned it. I'm not sure what the exact type of socket/plug he will be using is - anyone on here know what the standard is for this? (if any) (just so I'm happy this doesn't contravene any regs).

Thanks,

Colin


BS546 2A or 5A round pin plugs, the ones that date back at least as
far as the 1930s. They are still allowed. 2A ones look nicer imho.


NT

Colin Green June 12th 12 08:54 PM

Alternatives to downlighters in insulated flat roof .
 
On Sunday, June 10, 2012 11:35:46 PM UTC+1, NT wrote:
[...]

BS546 2A or 5A round pin plugs, the ones that date back at least as
far as the 1930s. They are still allowed. 2A ones look nicer imho.


Thanks. Seems like this might be a slightly unorthodox option, but a quick search shows they're still allowed (as you say) and I can buy these online so I'll run with this option. Not sure if the sparky was intending to use 2A or 5A, probably 5A from what I'm finding.

Colin

Andy Wade June 18th 12 07:55 PM

Alternatives to downlighters in insulated flat roof .
 
On 12/06/2012 20:54, Colin Green wrote:
On Sunday, June 10, 2012 11:35:46 PM UTC+1, NT wrote:
[...]

BS546 2A or 5A round pin plugs, the ones that date back at least as
far as the 1930s. They are still allowed. 2A ones look nicer imho.


Thanks. Seems like this might be a slightly unorthodox option, but a
quick search shows they're still allowed (as you say) and I can buy
these online so I'll run with this option. Not sure if the sparky was
intending to use 2A or 5A, probably 5A from what I'm finding.


It's quite orthodox in fact. The standard is BS 546:1950. In domestic
premises the socket outlets must be the shuttered type.

--
Andy