Radiator TRV's
I have a conservatory which is fitted with a radiator. The conservatory
never gets warm as the house heats up faster and reaches the room thermostat temperature and cuts off before the conservatory can get warm. The room thermostat is in the hall which also has a radiator. I have TRV's on all the radiators in the house bar the one in the hall. My plan is to fit a trv to the hall radiator and turn it down, along with the other room radiators. I will leave the conservator one turned up thus allowing the conservatory to warm up before the rest of the house reaches the desired temp. What I am asking is if there is any sort of problem with this. I have read that there shouldn't be a trv in the same room as the room thermostat. Thanks for any advice offered. Mark. |
#2
|
|||
|
|||
Radiator TRV's
My plan is to fit a trv to the hall radiator and turn it down,
along with the other room radiators. This won't work. If the hall TRV is set above the room thermostat, than the TRV will never operate. If the TRV is set below the room thermostat, the heating will never turn off and is the equivalent to shorting out the room thermostat. This will keep the conservatory warm. However, the boiler will remain on constantly, even when no heat is required, costing you a fortune if the boiler cutout doesn't operate. The only solution that will really be satisfactory in your situation is to have a separate zone for the conservatory. This means that the conservatory will have its own programmable thermostat totally independent from the rest of the house. It also allows different time scales to be used. If, for example, the conservatory is used as a dining room, the timer can be set to only heat it for the early evening, saving you loads in keeping a poorly insulated conservatory hot for the entire day and evening. Another alternative is to have TRVs in every room and remove the room thermostat. Then an automatic bypass loop is used (any old manual one removed) with a flow switch that can turn off the boiler when the automatic bypass opens. This solution is not as good, as there isn't separate timing for the conservatory. However, it may be easier to implement if the pipework isn't conducive to sub zoning. Christian. |
#3
|
|||
|
|||
Radiator TRV's
Christian McArdle wrote:
My plan is to fit a trv to the hall radiator and turn it down, along with the other room radiators. This won't work. If the hall TRV is set above the room thermostat, than the TRV will never operate. If the TRV is set below the room thermostat, the heating will never turn off and is the equivalent to shorting out the room thermostat. This will keep the conservatory warm. However, the boiler will remain on constantly, even when no heat is required, costing you a fortune if the boiler cutout doesn't operate. But they do. I ran my old house like that for 6 years no problem. TRV's on all rads except bathroom, and stat on max. the PUMP runs all the time. The boiler does not...eventually there is just one super hot bathroom, and the pipes going to it, and the boiler occasionally firing up to keep it that way. Short of a zone for every room with its own thermostat, its actually the best way to do it. You CAN balance everything and hope that the heat losses stay teh same, and the master stat will do everything right, but its a darned sight cheaper to TRV everything, so you can turn down certain rooms when not in use. The only solution that will really be satisfactory in your situation is to have a separate zone for the conservatory. This means that the conservatory will have its own programmable thermostat totally independent from the rest of the house. It also allows different time scales to be used. If, for example, the conservatory is used as a dining room, the timer can be set to only heat it for the early evening, saving you loads in keeping a poorly insulated conservatory hot for the entire day and evening. I disagree.. Another alternative is to have TRVs in every room and remove the room thermostat. Then an automatic bypass loop is used (any old manual one removed) with a flow switch that can turn off the boiler when the automatic bypass opens. This solution is not as good, as there isn't separate timing for the conservatory. However, it may be easier to implement if the pipework isn't conducive to sub zoning. That is pretty much what I suggested. Except why remove the stat? Just whack it up to full...and the auto bypass? That's a neat idea..except that without the pump running all the time, and using the boiler to monitor flow temp, how does it know when to cut in again? All I can say is the bodge described WORKS. Short of re-engineering everything, its a good compromise between economy, cost of installation, and pump life. Its IMHO the best compromise to upgrading an existing system to get better control over room temps without going to a proper fully zoned system complete with loads of motorised valves and thermostats, which need a lot of wiring as well as re-plumbing. Christian. |
#4
|
|||
|
|||
Radiator TRV's
The boiler does not...eventually there is just one super hot
bathroom, and the pipes going to it, and the boiler occasionally firing up to keep it that way. It is against the building regulations to install such a system. It keeps the bathroom too hot and the central heating pipes hot when they could be cold. Central heating pipes do lose a lot of heat. You CAN balance everything and hope that the heat losses stay teh same, and the master stat will do everything right, but its a darned sight cheaper to TRV everything, so you can turn down certain rooms when not in use. You can TRV every room except the room thermostat one. Balance the system properly and then turn down the room thermostat room half a turn. This ensures that other rooms warm up quicker and the TRVs shut off before the room thermostat is satisfied. Then, when this happens, the boiler interlock cuts in, preventing the central heating pipes being kept warm for no reason, which can be very wasteful, particularly on a marginal day when heating is only really required in the morning and late evening, but is selected on all day. Christian. |
#5
|
|||
|
|||
Radiator TRV's
"Christian McArdle" wrote in message t... The boiler does not...eventually there is just one super hot bathroom, and the pipes going to it, and the boiler occasionally firing up to keep it that way. It is against the building regulations to install such a system. It keeps the bathroom too hot and the central heating pipes hot when they could be cold. Central heating pipes do lose a lot of heat. You CAN balance everything and hope that the heat losses stay teh same, and the master stat will do everything right, but its a darned sight cheaper to TRV everything, so you can turn down certain rooms when not in use. You can TRV every room except the room thermostat one. Balance the system properly and then turn down the room thermostat room half a turn. This ensures that other rooms warm up quicker and the TRVs shut off before the room thermostat is satisfied. Then, when this happens, the boiler interlock cuts in, preventing the central heating pipes being kept warm for no reason, which can be very wasteful, particularly on a marginal day when heating is only really required in the morning and late evening, but is selected on all day. Sounds right to me. So as a compromise, how about putting a wireless stat in the conservatory and replacing the stat in the hall with a TRV on the hall radiator? The timer would ensure that you're not trying to heat the conservatory all the time. And you might need to set the conservatory stat down a bit lower than you'd have set it were it still in the hall. Seems to me it would be easier than rejigging the CH to add an additional zone, and avoid having the system running all the time. Just my 2p Cheers Clive |
#6
|
|||
|
|||
Radiator TRV's
Sounds right to me. So as a compromise, how about putting a wireless stat
in the conservatory and replacing the stat in the hall with a TRV on the hall radiator? Whilst this would work, it has the very serious problem that the radiator in the thermostat room shouldn't not be controllable (i.e. should have lockshields both ends). By putting an unzoned thermostat in the conservatory, you are basically removing the ability to turn off conservatory heating. OK, will some of the other solutions you don't have independent timing, but at least you could manually control it. Christian. |
#7
|
|||
|
|||
Radiator TRV's
Christian McArdle wrote:
The boiler does not...eventually there is just one super hot bathroom, and the pipes going to it, and the boiler occasionally firing up to keep it that way. It is against the building regulations to install such a system. It keeps the bathroom too hot and the central heating pipes hot when they could be cold. Central heating pipes do lose a lot of heat. Firstly I don't think its against regs, secondly it doesn't keep the pipes hot. As the TRVs close the loops to which they are attached **** down, flow stops, and the pipes cool..only the bathrom loop stahs hot, and in my case, this was a positive advantage, cos it kept the bathroom floor warm as well. You CAN balance everything and hope that the heat losses stay teh same, and the master stat will do everything right, but its a darned sight cheaper to TRV everything, so you can turn down certain rooms when not in use. You can TRV every room except the room thermostat one. Balance the system properly and then turn down the room thermostat room half a turn. This ensures that other rooms warm up quicker and the TRVs shut off before the room thermostat is satisfied. Then, when this happens, the boiler interlock cuts in, preventing the central heating pipes being kept warm for no reason, which can be very wasteful, particularly on a marginal day when heating is only really required in the morning and late evening, but is selected on all day. Well for a start I had assumed we were time clocked anyway, secondly what the heck? As long as teh pump has somewhere to pump, you cabn even have a trickle bypass on it so that all teh rads are TRV'ed. There is absolutley NO problem with the pump running all the time, because the TRV';s will stop the flow in unwanted pipe sections. That is, after all, what they do.Ther will be far less loss through a few lagged pipes than vast areas of radiator heating unused rooms needlessly anyway. No mate. I don't buy it. Christian. |
#8
|
|||
|
|||
Radiator TRV's
Ok quite a few ideas for me to consider there !! And all much more knowledgeable than I ! Thanks for all your ideas, that'll give me something to pick through and start to investigate. Oh, and sorry for the double post. Cheers all, Mark. |
#9
|
|||
|
|||
Radiator TRV's
Ther will be far less loss through a few lagged pipes than vast
areas of radiator heating unused rooms needlessly anyway. But what turns the boiler off? The approved document requires a boiler interlock that turns the boiler off when no heat is required. You may think it OK to reduce your overall efficiency by around 10% by running the boiler when all the radiators are off, but the government disagrees. Christian. |