  #1   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,016
Default Main bonding in gas meter box

I want to fit a main bonding clamp in an external gas meter box. The
box doesn't have a cable entry point. I've read that in these circs.
one mustn't drill the box but must take the cable up through the hole
for the consumer-side gas pipe. Is that right please? If so, does the
cable need to be in conduit? (I think it'll look bloody naff either
way.)

And while I'm here, does the meter box count as "damp conditions" where
I can't use an E14 clamp pl?
--
Robin
reply to address is (meant to be) valid


  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 3,565
Default Main bonding in gas meter box

On Apr 2, 11:14*pm, "Robin" wrote:
I want to fit a main bonding clamp in an external gas meter box. *The
box doesn't have a cable entry point. *I've read *that in these circs..
one mustn't drill the box but must take the cable up through the hole
for the consumer-side gas pipe. *Is that right please? *If so, does the


The bonding should be done where the service enters the house.
Sometimes in the gas cab isnt the right place.


cable need to be in conduit? *(I think it'll look bloody naff either
way.)


No, not unless I've missed something all this time.

And while I'm here, does the meter box count as "damp conditions" where
I can't use an E14 clamp pl?


Well, it will be damp, so an outdoor one would be best.


NT
  #3   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 848
Default Main bonding in gas meter box

NT wrote:
The bonding should be done where the service enters the house.


"Where it enters" says to me just immediately before it goes through
the brickwork, ie on the outside of the brickwork. Does it actually
mean "immediately after it enters", ie on the inside of the brick
work? Certainly all the bonding clamps I've ever encountered are
immediately after the service enters - *and* on the consumer side
of any cut-off tap. After all, it's to bond the internal pipework,
not to use the external pipework as a ground.

JGH
  #4   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 1,307
Default Main bonding in gas meter box

jgharston wrote:

NT wrote:
The bonding should be done where the service enters the house.


"Where it enters" says to me just immediately before it goes through
the brickwork, ie on the outside of the brickwork. Does it actually
mean "immediately after it enters", ie on the inside of the brick
work? Certainly all the bonding clamps I've ever encountered are
immediately after the service enters - *and* on the consumer side
of any cut-off tap. After all, it's to bond the internal pipework,
not to use the external pipework as a ground.


544.1.2
"connection...As near as practicable to the point of entry...on the
consumers hard metal pipework...before any branch pipework....within
600mm of meter outlet union, or point of entry if meter is external."

So,before any branches, preferably within 600mm of entry for the OP, and
within 600mm if the meter is internal, on the consumer side, not the gas
supply side.



--
To reply by e-mail, change the ' + ' to 'plus'.
  #5   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,016
Default Main bonding in gas meter box

544.1.2
"connection...As near as practicable to the point of entry...on the
consumers hard metal pipework...before any branch pipework....within
600mm of meter outlet union, or point of entry if meter is external."


Thanks Alan. Yes, reg 544.1.2 seems to leave it open as it whether the
bonding is inside or outside (where, as here, it's a simple case of a
pipe through a wall, nothing buried etc). But there's also the gas
regs. If there's no bonding visible in the meter cabinet a gas fitter
may mark it "Not To Current Standards" based on GasSafe's
view of the gas regs
(http://www.gassaferegister.co.uk/pdf/Gas_Industry_Unsafe_Situations_Procedure.pdf)
The bonding has also to be accessible and the pipe inside the house is
difficult to access as it enter under a corner of the living room floor.
So I thought
I'd take the opportunity while the floor's up to loop through from
inside to the meter box and try to keep everyone happy.




--
Robin
reply to address is (meant to be) valid







  #6   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 3,565
Default Main bonding in gas meter box

On Apr 3, 7:49*am, "Robin" wrote:
544.1.2
"connection...As near as practicable to the point of entry...on the
consumers hard metal pipework...before any branch pipework....within
600mm of meter outlet union, or point of entry if meter is external."


Thanks Alan. *Yes, reg 544.1.2 seems to leave it open as it whether the
bonding is inside or outside (where, as here, it's a simple case of a
pipe through a wall, nothing buried etc). *But there's also the gas
regs. *If there's no *bonding visible in the meter cabinet a gas fitter
may mark it "Not To Current Standards" based on GasSafe's
view of the gas regs
(http://www.gassaferegister.co.uk/pdf/Gas_Industry_Unsafe_Situations_P....)
The bonding has also to be accessible and the pipe inside the house is
difficult to access as it enter under a corner of the living room floor.
So I thought
I'd take the opportunity while the floor's up to loop through from
inside to the meter box and try to keep everyone happy.


Can that be right, given that some cas meter cabs are more than 60cm
from the house?


NT
  #7   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 7,688
Default Main bonding in gas meter box

Robin wrote:
I want to fit a main bonding clamp in an external gas meter box. The
box doesn't have a cable entry point. I've read that in these circs.
one mustn't drill the box but must take the cable up through the hole
for the consumer-side gas pipe. Is that right please? If so, does
the cable need to be in conduit? (I think it'll look bloody naff
either way.)

And while I'm here, does the meter box count as "damp conditions"
where I can't use an E14 clamp pl?


Are you coming through the rear of the gas box or externally? I don't know
of any reason not to drill the box if external, but

http://www.eca.co.uk/training-news-a...s-meter-boxes/

and

http://www.eca.co.uk/_assets/files/B...tallations.pdf

apply for rear entry cables (we have them posted on the wall at work as a
reminder).

Anyway, a true pro would not drill the box. He would us a PZ2 screwdriver
and a hammer to make the hole:-).

I would consider condensation (and possibly frost) would make the clamps
liable to damp.

--
Adam


  #8   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 1,683
Default Main bonding in gas meter box

EC15 under Ebay 300653435050 is £1.69 delivered.

Terminating an EC outside is common for externally run pipework, such
as Tracpipe used to replace internal lead.
  #9   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,016
Default Main bonding in gas meter box

Are you coming through the rear of the gas box or externally?

I have to bring the cable out below the box (because of the stupid way
it was mounted by BG).

http://www.eca.co.uk/training-news-a...s-meter-boxes/

Bullseye: example A3 is what I've got so I'll take it as a model.

Anyway, a true pro would not drill the box. He would us a PZ2
screwdriver and a hammer to make the hole:-).


Thanks but I know my place - ie an amateur certain only of my ability
to shatter the 20-year old box with one misjudged blow.

--
Robin
reply to address is (meant to be) valid


  #10   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,016
Default Main bonding in gas meter box

EC15 under Ebay 300653435050 is £1.69 delivered.

Ta.
--
Robin
reply to address is (meant to be) valid


Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Running main bonding conductor sm_jamieson UK diy 7 April 7th 11 09:22 PM
Main equipotential bonding Tabby UK diy 6 October 1st 10 04:33 PM
Main Earth bonding to lead gas pipe. chris French UK diy 4 May 5th 10 11:32 AM
Connections for main earth bonding to gas/water? Lobster UK diy 6 February 5th 07 08:11 PM
Cross-bonding/earth bonding gas meter Jim UK diy 1 July 28th 06 10:19 PM


All times are GMT +1. The time now is 06:31 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"