Default 20mm-wide twin-core & earth cable: 10 sq.mm or 16 sq.mm?


There is some flat, twin-core and earth cable in my house that is 20mm
wide, overall. Would that be 16 sq.mm cable or 10 sq.mm? It's the
standard white-covered pre-2006 stuff.

Thanks,

Dave H
  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 25,191
Default 20mm-wide twin-core & earth cable: 10 sq.mm or 16 sq.mm?

Dave H wrote:
There is some flat, twin-core and earth cable in my house that is 20mm
wide, overall. Would that be 16 sq.mm cable or 10 sq.mm? It's the
standard white-covered pre-2006 stuff.


Sounds like 16mm^2 to me:

CSA (CPC) Strands Overall
mm^2 No./dia. mm approx.
--------- ------- ----------
1.0 (1.0) 1/1.13 4.5 x 8.2
1.5 (1.0) 1/1.38 4.7 x 8.2
2.5 (1.5) 1/1.78* 5.3 x 9.9
4.0 (1.5) 7/0.85 6.1 x 11.4
6.0 (2.5) 7/1.04 6.8 x 13.1
10 (4.0) 7/1.35 8.4 x 16.8
16 (6.0) 7/1.71 9.6 x 19.5
* or 7/0.67



--
Cheers,

John.

/================================================== ===============\
| Internode Ltd - http://www.internode.co.uk |
|-----------------------------------------------------------------|
| John Rumm - john(at)internode(dot)co(dot)uk |
\================================================= ================/
  #3   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 1,283
Default 20mm-wide twin-core & earth cable: 10 sq.mm or 16 sq.mm?


"Dave H" wrote

There is some flat, twin-core and earth cable in my house that is 20mm
wide, overall. Would that be 16 sq.mm cable or 10 sq.mm? It's the
standard white-covered pre-2006 stuff.

It is important that you check the conductor size itself on these issues.
Some modern cable has significantly less insulation than was applied to the
same "size" just 20 years ago!
I recently replaced some damaged 6mm cooker cable and was so surprised at
the change in over-insulation size that I had to mic the conductors up to be
sure.

Phil


  #4   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2
Default 20mm-wide twin-core & earth cable: 10 sq.mm or 16 sq.mm?

On Mon, 23 Apr 2007 02:34:40 +0100, John Rumm
wrote:

Sounds like 16mm^2 to me:

CSA (CPC) Strands Overall
mm^2 No./dia. mm approx.
--------- ------- ----------
1.0 (1.0) 1/1.13 4.5 x 8.2
1.5 (1.0) 1/1.38 4.7 x 8.2
2.5 (1.5) 1/1.78* 5.3 x 9.9
4.0 (1.5) 7/0.85 6.1 x 11.4
6.0 (2.5) 7/1.04 6.8 x 13.1
10 (4.0) 7/1.35 8.4 x 16.8
16 (6.0) 7/1.71 9.6 x 19.5
* or 7/0.67


Great - thank you! (Likewise to theScullster)
DaveH

Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Connection armoured calbe to twin and earth cable Lawrence Zarb UK diy 5 March 1st 07 09:45 AM
reusing earth wire in a 5-core cable Geronimo W. Christ Esq UK diy 13 November 9th 06 08:28 PM
join thin twin electricity cable with standard twin and earth Dundonald UK diy 6 March 29th 05 09:00 AM
1mm Twin earth cable query Pedge UK diy 26 January 29th 05 02:34 PM
Twin Core and Earth.... Derek Doormer UK diy 19 December 9th 04 09:11 AM


All times are GMT +1. The time now is 03:15 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"