Replace 3-pin with 2-pin shaver plug
I've got a Wahl hair clipper set with 3-pin plug but it would be a lot
more convenient if I could plug it into the shaver socket instead of dragging out the extension cable. The lead is twin flex. The plug (marked 13A) has a 3A fuse and the unit is rated at 240v 9W. Is there any reason not to put a two pin shaver plug on it? Many thanks -- AnthonyL |
Replace 3-pin with 2-pin shaver plug
|
Replace 3-pin with 2-pin shaver plug
On Fri, 02 Mar 2007 18:47:09 +0000, Lurch
wrote: On Fri, 02 Mar 2007 18:29:03 GMT, lid (AnthonyL) mused: I've got a Wahl hair clipper set with 3-pin plug but it would be a lot more convenient if I could plug it into the shaver socket instead of dragging out the extension cable. The lead is twin flex. The plug (marked 13A) has a 3A fuse and the unit is rated at 240v 9W. Is there any reason not to put a two pin shaver plug on it? Technically not. The shaver socket will most probably be rated at about 20VA so should be fine. I'm sure there are probably other reasons why you shouldn't do it though. I suppose I might in theory invalidate the guarantee. -- AnthonyL |
Replace 3-pin with 2-pin shaver plug
On Fri, 02 Mar 2007 18:47:09 +0000 someone who may be Lurch
wrote this:- I've got a Wahl hair clipper set with 3-pin plug [snip] Is there any reason not to put a two pin shaver plug on it? Technically not. The shaver socket will most probably be rated at about 20VA so should be fine. One would need to get hold of the plug from somewhere, or cannibalise a suitable lead with the plug already on it. -- David Hansen, Edinburgh I will *always* explain revoked encryption keys, unless RIP prevents me http://www.opsi.gov.uk/acts/acts2000/00023--e.htm#54 |
Replace 3-pin with 2-pin shaver plug
In article ,
David Hansen wrote: Technically not. The shaver socket will most probably be rated at about 20VA so should be fine. One would need to get hold of the plug from somewhere, or cannibalise a suitable lead with the plug already on it. Something like this might be the cheapest option. http://www.rapidonline.com/productin...moduleno=65237 -- *If tennis elbow is painful, imagine suffering with tennis balls * Dave Plowman London SW To e-mail, change noise into sound. |
Replace 3-pin with 2-pin shaver plug
On Sat, 03 Mar 2007 10:46:04 +0000 (GMT), "Dave Plowman (News)"
mused: In article , David Hansen wrote: Technically not. The shaver socket will most probably be rated at about 20VA so should be fine. One would need to get hold of the plug from somewhere, or cannibalise a suitable lead with the plug already on it. Something like this might be the cheapest option. long link was here I'd say that would be the best option, would mean some dismantling of the machine though if it hasn't already got a figure 8 inlet socket. I would defnitley not recommend joining the flex in any form in this situation. -- Regards, Stuart. |
Replace 3-pin with 2-pin shaver plug
|
Replace 3-pin with 2-pin shaver plug
"Dave Plowman (News)" wrote in message ... In article , David Hansen wrote: Technically not. The shaver socket will most probably be rated at about 20VA so should be fine. One would need to get hold of the plug from somewhere, or cannibalise a suitable lead with the plug already on it. Something like this might be the cheapest option. http://www.rapidonline.com/productin...moduleno=65237 I doubt that will fit a shaver socket if it is a standard European 2 pin plug, that are not the same (Try plugging a shaver into a euro socket, they don't fit. IIRC the shaver plugs have fatter pins that are closer together. Sparks... |
Replace 3-pin with 2-pin shaver plug
On 2 Mar, 18:29, (AnthonyL) wrote:
I've got a Wahl hair clipper set with 3-pin plug but it would be a lot more convenient if I could plug it into the shaver socket instead of dragging out the extension cable. The lead is twin flex. The plug (marked 13A) has a 3A fuse and the unit is rated at 240v 9W. Is there any reason not to put a two pin shaver plug on it? Many thanks If the appliance is 2 core, not 3, and under 20w, no problem. Note shaver transformers are rated for short use times only. You can use either the old British 2 pin plugs popular in the 20s, and still used with shavers today, or the old French 2 pin plugs will also fit more or less all shaver adaptors. The latter have thinner pins slightly wider spaced. NT |
Replace 3-pin with 2-pin shaver plug
|
Replace 3-pin with 2-pin shaver plug
On Sat, 03 Mar 2007 11:32:54 +0000, Lurch
wrote: On Sat, 03 Mar 2007 10:46:04 +0000 (GMT), "Dave Plowman (News)" mused: In article , David Hansen wrote: Technically not. The shaver socket will most probably be rated at about 20VA so should be fine. One would need to get hold of the plug from somewhere, or cannibalise a suitable lead with the plug already on it. Something like this might be the cheapest option. long link was here I'd say that would be the best option, would mean some dismantling of the machine though if it hasn't already got a figure 8 inlet socket. I would defnitley not recommend joining the flex in any form in this situation. No need at all. The existing plug unscrews and I've got a suitable 2 pin plug to screw back on. I certainly would not be trying to join up mains cable for a hand held device used in the bathroom! My concerns were the use of the shaver socket and the loss of the fuse which have been covered elsewhere. -- AnthonyL |
Replace 3-pin with 2-pin shaver plug
|
All times are GMT +1. The time now is 08:49 PM. |
Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004 - 2014 DIYbanter