Default Honeywell CM Zone problems HR80 -HC60NG

Any experts on the Honeywell CM Zone heating control system?

I can't get my HR80 radiator controller modules to communicate with an
existing HC60NG relay module. The CM67z room unit and three HR80's were
bought as a pack in Germany recently. The HC60NG boiler control unit
came with a CM67NG RF room controller (model reference T6667D1081),
bought about four years ago in the UK.

The CM67z will correctly set the HR80 programmable temperatures and the
CM67z can communicate with the HC60NG, at least if I set parameter
17:SU to 1 or 2 (which automatically sets 7:tS to 2) before doing the
binding. However the CM67z with the factory default settings won't bind
to the HC60NG. The HR80's won't switch the HC60NG output ON whatever
temperature I set manually. I've tried clearing all the bindings and
running through all the teach-ins from zero but I am still stuck.

Any ideas? I wonder if the HC60NG is too old to receive data from the
HR80's but I don't want to go and invest £60 in a new HC60NG if it is
not the problem.

  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 48
Default Honeywell CM Zone problems HR80 -HC60NG


Have you tried Honeywell themselves?


  #3   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 4
Default Honeywell CM Zone problems HR80 -HC60NG


hzatph wrote:
Have you tried Honeywell themselves?

Yes but they weren't very helpful. Their support seems to be ony for
professional installers.

  #4   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 66
Default Honeywell CM Zone problems HR80 -HC60NG


wrote in message
oups.com...
Any experts on the Honeywell CM Zone heating control system?

I can't get my HR80 radiator controller modules to communicate with an
existing HC60NG relay module. The CM67z room unit and three HR80's were
bought as a pack in Germany recently. The HC60NG boiler control unit
came with a CM67NG RF room controller (model reference T6667D1081),
bought about four years ago in the UK.

The CM67z will correctly set the HR80 programmable temperatures and the
CM67z can communicate with the HC60NG, at least if I set parameter
17:SU to 1 or 2 (which automatically sets 7:tS to 2) before doing the
binding. However the CM67z with the factory default settings won't bind
to the HC60NG. The HR80's won't switch the HC60NG output ON whatever
temperature I set manually. I've tried clearing all the bindings and
running through all the teach-ins from zero but I am still stuck.

Any ideas? I wonder if the HC60NG is too old to receive data from the
HR80's but I don't want to go and invest £60 in a new HC60NG if it is
not the problem.


Go find a scanner, I seem to remember that the new generation of the CM67
are on a higher frequency band, 868 MHz cmpared to 433 MHz...
http://content.honeywell.com/UK/home.../cmx/HC026.pdf

could this be the problem?



  #5   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 4
Default Honeywell CM Zone problems HR80 - HC60NG


James Salisbury wrote:
Go find a scanner, I seem to remember that the new generation of the CM67
are on a higher frequency band, 868 MHz cmpared to 433 MHz...
http://content.honeywell.com/UK/home.../cmx/HC026.pdf

could this be the problem?


Thanks for all the suggestions.

I got a friend to email the very efficient Honeywell German customer
service and they replied within a few hours. They're a lot more
knowlegable than their British counterparts when it come to CM Zone. It
turns out that my HC60NG/R6660D boiler control has software that is too
old to function correctly with the CM67z and HR80. You can tell which
software you have by looking at the code on the NEC microcontroller on
the circuit board. It needs to be version 1.82 or more recent and not
1.88 (perhaps a typing error as the version numbers are not
increasing?) . As it is impossible to update the software, the only
solution is to buy a new HC60NG. Mind you, nowhere on the Honeywell
site does it hint that not all HC60NG are compatible with the CM Zone.

Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Hot water/ Heating wiring problems bachippy UK diy 3 May 30th 06 01:33 PM
Linux is Driving me $#@!!!! nutz!!! Gunner Metalworking 115 January 14th 06 07:49 PM
Honeywell V4073A problems barrowfordred UK diy 2 March 11th 05 09:03 AM
Honeywell Smartfit Base Unit Problems RossG UK diy 2 December 22nd 04 02:06 AM
Honeywell 3 port mid position valve - problems with... Jerry. UK diy 14 February 20th 04 04:39 PM


All times are GMT +1. The time now is 12:12 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"