Bathroom reorganisation. I need to route the waste pipe from the basin
to the outside wall, but in the way there will be a new corner shower
unit. I want the shower tray sitting directly on the floor so there's no
appreciable height difference when stepping in or out of the shower.

The house is substantial, about 200 years old, with very uneven walls
and floors.

Things I've thought of, not necessarily sensible, a

* stud the wall behind the shower out a couple of inches and run the
pipe though the gap

* cut a channel in the wall, which is single-leaf brick

* cut a channel though the shower base, which is acrylic

* notch the joists and strengthen them as necessary - I will be putting
thick plywood and a limestone floor on top of them

Comments?

--
Mike Barnes
  #2   Report Post  
Nick Finnigan
 
Posts: n/a
Default Routing waste pipe past shower tray

"Mike Barnes" wrote in message
...

Bathroom reorganisation. I need to route the waste pipe from the basin
to the outside wall, but in the way there will be a new corner shower
unit. I want the shower tray sitting directly on the floor so there's no
appreciable height difference when stepping in or out of the shower.


* notch the joists and strengthen them as necessary - I will be putting
thick plywood and a limestone floor on top of them


I guess you will have to do that for the shower waste anyway?
Can you go from the basin along the internal wall (boxed in)
to the shower, then down through the limestone and plywood,
through a joist or two and join up with the shower waste?



  #3   Report Post  
Simon Avery
 
Posts: n/a
Default Routing waste pipe past shower tray

Mike Barnes wrote:

Hello Mike

MB| Bathroom reorganisation.


Commiserations. I've got to do mine this winter too.

OTOH, I've just discovered that the walled-in section I want to put
the shower is EXACTLY 1200mm across, which is EXACTLY the width of a
standard double tray so I don't need bespoke or homebuilt trays. Not
often that something like that happens! Not like it was intentional,
either. It's also 900mm deep, another standard size. Worrying.

MB| a new corner shower unit. I want the shower tray sitting
MB| directly on the floor so there's no appreciable height
MB| difference when stepping in or out of the shower.


Ah, that buggers up the normal method of boxing it up 2-3" and running
everything through the boxing. Sure you don't want to do this?

MB| * stud the wall behind the shower out a couple of inches
MB| and run the
MB| pipe though the gap


Possible, and probably the least hassle. You don't mention the shower
feeds, but you may be able to use this for them too, making a neater
finish.

MB| * cut a channel in the wall, which is single-leaf brick


Absolutely not.

MB| * cut a channel though the shower base, which is acrylic


Absolutely not, for it'll weaken it dramatically, make it bendy and
it'll split shortly after.

MB| * notch the joists and strengthen them as necessary - I
MB| will be putting
MB| thick plywood and a limestone floor on top of them


Unless they're particularly thick joists, I'd not do this as the
limestone will be adding a lot of weight and you don't want to be
weakening them unduly.

MB| Comments?


The first seems the best, and worthwhile adding some kind of
inspection/access panel if you possibly can (and not doing any tiling,
flooring until you're 100% sure it's working properly) I'd use
solvent weld for the waste as it doesn't tend to leak like compression
sometimes can.

--
Simon Avery, Dartmoor, UK
uk.d-i-y FAQ: http://www.diyfaq.org.uk/

  #4   Report Post  
Matt Beard
 
Posts: n/a
Default Routing waste pipe past shower tray

(Simon Avery) wrote in message ...
Mike Barnes wrote:
snip
MB| * notch the joists and strengthen them as necessary - I
MB| will be putting
MB| thick plywood and a limestone floor on top of them


Unless they're particularly thick joists, I'd not do this as the
limestone will be adding a lot of weight and you don't want to be
weakening them unduly.

MB| Comments?


snip


The Building Research Establishment do a "Defect Action Sheet" number
DAS 99 on the issue of notching and drilling joists in a way to
produce the minimum weakening.

A brief summary is:

Notches can be cut in the top of a joist in an area that stretches
from 7% of the span from one support to 25% of the span from the same
support. The notch must be no deeper than the lesser of 12.5% of the
depth of the joist or 250mm. There is a matching "notch zone" at the
other end of the joist.

Holes can be drilled in a zone that starts a distance of 25% of the
span from one support and ends 40% from the same end. The zone extends
from the centre line of the joist up 12.5% of the joist height and
down 12.5% of the joist height. There is a matching "hole zone" at
the other end of the joist. Holes must be spaced such that the
distance between centres is at least 3 times the diameter of each hole
(I guess if the holes are different sizes you take the larger
diameter).

They don't say how close notches and holes can get at the 25% point,
but I would say "as far away as you can keep them".

This is my interpretation of the document, not an official "you can do
it this way". If you want to be sure you could try contacting the
Building Research Establishment in Watford or your local planning
office (shudder!)
  #5   Report Post  
Nick Finnigan
 
Posts: n/a
Default Routing waste pipe past shower tray

"Matt Beard" wrote in message
om...

Notches can be cut in the top of a joist in an area that stretches
from 7% of the span from one support to 25% of the span from the same
support. The notch must be no deeper than the lesser of 12.5% of the
depth of the joist or 250mm.


That just about rules out notches for waste pipes then.




  #6   Report Post  
Mike Barnes
 
Posts: n/a
Default Routing waste pipe past shower tray

In uk.d-i-y, Matt Beard wrote:
The Building Research Establishment do a "Defect Action Sheet" number
DAS 99 on the issue of notching and drilling joists in a way to
produce the minimum weakening.

A brief summary is:

Notches can be cut in the top of a joist in an area that stretches
from 7% of the span from one support to 25% of the span from the same
support. The notch must be no deeper than the lesser of 12.5% of the
depth of the joist or 250mm. There is a matching "notch zone" at the
other end of the joist.

Holes can be drilled in a zone that starts a distance of 25% of the
span from one support and ends 40% from the same end. The zone extends
from the centre line of the joist up 12.5% of the joist height and
down 12.5% of the joist height. There is a matching "hole zone" at
the other end of the joist. Holes must be spaced such that the
distance between centres is at least 3 times the diameter of each hole
(I guess if the holes are different sizes you take the larger
diameter).

They don't say how close notches and holes can get at the 25% point,
but I would say "as far away as you can keep them".

This is my interpretation of the document, not an official "you can do
it this way". If you want to be sure you could try contacting the
Building Research Establishment in Watford or your local planning
office (shudder!)


Thanks, excellent stuff. The bad news is that that formula allows only a
16 mm notch. Actually I'm pretty sure that there are holes and notches
outside those specifications under just about every floor I've ever
taken up :-( however I'm talking about substantial old houses where the
joists probably started out much stronger than they needed to be.

Thinking on, I wonder if some reinforcement might help. Two steel plates
say 600x100 with a 50 diameter hole in the middle, put them either side
of the joist, bolt them through, then drill out the wood. Obviously I'd
want someone qualified to do the sums but I'm still at the ideas stage.

A previous house had one joist on the ground floor not unlike that. I
could see it from the cellar. The end of the joist had obviously rotted
so someone had made a new piece about 600 mm long, butted it up to the
original, and bolted the two pieces together using steel cheeks.

--
Mike Barnes
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Iron Waste Pipe BillR UK diy 9 August 28th 03 06:55 PM
pipe bending to make a shower 'rail' NC UK diy 19 August 16th 03 04:32 PM
Connecting jets, shower arm direct to pipe Kevin Murphy UK diy 7 July 15th 03 11:10 PM
Washing machine - waste pipe limescale IMM UK diy 2 July 15th 03 10:25 PM


All times are GMT +1. The time now is 10:21 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"