I know that gas pipes passing through cavity walls need to be sleeved
and sealed to the sleeving to prevent gas escaping into the cavity in
the event of a leak.

What about gas pipes passing through a plasterboard ceiling and the
floorboards above? Is there a similar requirement for the same reason?

Are there any specifications as to what the sleeving material should
be? The pipe will be 28mm copper, so will 32mm waste pipe be OK?

TIA

Mr F.

  #2   Report Post  
Andy
 
Posts: n/a
Default


"Mr Fizzion" wrote in message
...
I know that gas pipes passing through cavity walls need to be sleeved
and sealed to the sleeving to prevent gas escaping into the cavity in
the event of a leak.

What about gas pipes passing through a plasterboard ceiling and the
floorboards above? Is there a similar requirement for the same reason?

Are there any specifications as to what the sleeving material should
be? The pipe will be 28mm copper, so will 32mm waste pipe be OK?

TIA

Mr F.


I don't know the answer, but can imagine it will be complicated by the
probable existence of another regulation to prevent fire penetrating a
ceiling via a hole.
That is why I am wondering whether you can use plastic sleeving.

Andy.


  #5   Report Post  
Aidan
 
Posts: n/a
Default


Mr Fizzion wrote:

What about gas pipes passing through a plasterboard ceiling and the
floorboards above? Is there a similar requirement for the same reason?


I was waiting in the hope of a reply from someone who is Corgi
registered. IMHO it needs to be sleeved, to prevent the accumulation of
gas, from an otherwise insignificant leak, in an unvented floor void.
One end would be left open to allow gas into a room, where it could be
smelt before it reached a hazardous concentration. The other end is
sealed with flexible mastic & packing. The sleeve should be the same
material as the pipe. With large pipes (drains) you can get intumescent
collars to preserve the fire integrity of the structure.

All pipes passing through walls should be sleeved. It is to allow the
structure to move/settle without stressing the pipes.



  #6   Report Post  
Lurch
 
Posts: n/a
Default

On 27 Sep 2005 01:14:34 -0700, "Aidan" scrawled:


Mr Fizzion wrote:

What about gas pipes passing through a plasterboard ceiling and the
floorboards above? Is there a similar requirement for the same reason?


I was waiting in the hope of a reply from someone who is Corgi
registered. IMHO it needs to be sleeved, to prevent the accumulation of
gas, from an otherwise insignificant leak, in an unvented floor void.


IANARCGI, but I don't think it does need sleeving. How many gas pipes
under floors do you see sleeved for their entire length then vented
into a room?
--
Stuart @ SJW Electrical

Please Reply to group
  #7   Report Post  
Aidan
 
Posts: n/a
Default


Lurch wrote:

IANARCGI, but I don't think it does need sleeving. How many gas pipes
under floors do you see sleeved for their entire length then vented
into a room?


Very true. I'd think most such stuff was pre-corgi when a gas fire in
upstairs rooms was commonplace. I'd think the current regulations would
be that such an installation would require the floor cavity to be
ventilated.

If there were no joints within the thickness of the floor, there would
be a miniscule risk of a leak. I still think that legally you should
sleeve it, there is a forseeable and avoidable risk of a leak into the
unventilated floor void. Running gas pipes in an unventilated void is
verboten.

  #8   Report Post  
Lurch
 
Posts: n/a
Default

On 27 Sep 2005 04:37:11 -0700, "Aidan" scrawled:


Lurch wrote:

IANARCGI, but I don't think it does need sleeving. How many gas pipes
under floors do you see sleeved for their entire length then vented
into a room?


Very true. I'd think most such stuff was pre-corgi when a gas fire in
upstairs rooms was commonplace. I'd think the current regulations would
be that such an installation would require the floor cavity to be
ventilated.

What have upstairs gas fires got to do with it? Gas pipes are run
under floors in new installations to feed boilers and fires located
downstairs as they aren't put under concrete floors.

If there were no joints within the thickness of the floor, there would
be a miniscule risk of a leak. I still think that legally you should
sleeve it, there is a forseeable and avoidable risk of a leak into the
unventilated floor void. Running gas pipes in an unventilated void is
verboten.


This, I cannot comment on as I don't know for sure but I have never
seen a sleeved gas pipe under a floor.
--
Stuart @ SJW Electrical

Please Reply to group
  #9   Report Post  
Aidan
 
Posts: n/a
Default


Lurch wrote:

What have upstairs gas fires got to do with it? Gas pipes are run
under floors in new installations to feed boilers and fires located
downstairs as they aren't put under concrete floors.


With suspended timber floors, the floor void is usually cross
ventilated with air bricks on the ground floor. The main purpose is to
evaporate any water from the ground, but there's no problem installing
gas pipes in such a ventilated floor void.

On upper floors, the floor void is not usually ventilated. You are not
now allowed to install gas pipes in or through an unventilated cavity.
That is what upstairs gas fires have to do with it.

  #10   Report Post  
Lurch
 
Posts: n/a
Default

On 27 Sep 2005 08:48:45 -0700, "Aidan" scrawled:


Lurch wrote:

What have upstairs gas fires got to do with it? Gas pipes are run
under floors in new installations to feed boilers and fires located
downstairs as they aren't put under concrete floors.


With suspended timber floors, the floor void is usually cross
ventilated with air bricks on the ground floor. The main purpose is to
evaporate any water from the ground, but there's no problem installing
gas pipes in such a ventilated floor void.

On upper floors, the floor void is not usually ventilated. You are not
now allowed to install gas pipes in or through an unventilated cavity.
That is what upstairs gas fires have to do with it.


What I meant was, in new installations all gas pipes are run under the
1st floor then dropped down to ground floor situated appliances so it
has nothing to do specifically with upstairs appliances. I haven't
seen a house built in the last 10 odd years that hasn't had its gas
services run in in this way.
--
Stuart @ SJW Electrical

Please Reply to group
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Are push fit plumbing fittings any good? Steve UK diy 75 September 3rd 05 01:56 PM
In Deep Sh*t.... Lobster UK diy 9 August 2nd 05 09:30 PM
electricity on my water pipes Laurent Doiron Home Repair 32 March 30th 04 06:01 PM
Joining Plastic Waste pipe to Lead pipe tinklemagoo UK diy 3 February 19th 04 05:34 AM
Sewer line replacement jeff Home Ownership 1 August 27th 03 03:24 AM


All times are GMT +1. The time now is 12:26 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"