DIYbanter

DIYbanter (https://www.diybanter.com/)
-   UK diy (https://www.diybanter.com/uk-diy/)
-   -   A leaky cold water tank (https://www.diybanter.com/uk-diy/103775-leaky-cold-water-tank.html)

cheesey_toastie April 21st 05 08:25 PM

A leaky cold water tank
 
Hi,

I'm new and have tried searching for the answer but it seems my problem
is too basic!

We noticed one of the the down pipes for the guttering was growing a
kind of mould, due to a constant supply of water running down it (and a
few plants growing in the gutter!).

I've traced the problem to the overflow for a small cold water tank in
the loft. It seems that the tank is warped and the water level is now
just over the overflow pipe.

Firstly what is this small tank for? The water in there seemed 'old'
and had sediment in the tank (which was easily stirred up just by
experimenting with the ball cock). I run all the water in the house
and couldnt make the tank empty as it all came from the huugae cold
water tank next to it. (this tank is about the same size as a toilet
cystern)

Secondly how to I go about adjusting the ball cock level so that it no
longer 'leaks'.

I noticed on this site everyone says 'find the outside water supply tap
before touching anything'. What am I look for here, a small man hole
cover?

Any help is much appreciated!!!

Cheesey Toastie


Steve Pearce April 22nd 05 10:26 AM

On 21 Apr 2005 12:25:39 -0700, "cheesey_toastie"
wrote:


Firstly what is this small tank for? The water in there seemed 'old'
and had sediment in the tank (which was easily stirred up just by
experimenting with the ball cock). I run all the water in the house
and couldnt make the tank empty as it all came from the huugae cold
water tank next to it. (this tank is about the same size as a toilet
cystern)

Secondly how to I go about adjusting the ball cock level so that it no
longer 'leaks'.


Sounds like it is the header tank for the cental heating. Adjusting
the ballcock usually requires bending the shaft.

Aidan April 22nd 05 11:09 AM

Agree, it's a 4 gallon feed and expansion tank for the heating. If it
has distorted, maybe it's had very hot water in it when the heating was
running; this would indicate a fault. It should always be cold.

You probably need to replace the washer in the float valve/ballcock. It
should have about 1" or 2" of water covering the outlet when the
heating system is cold, leaving about 3 gallons of airspace to
accomodate the expansion of the water when the system is hot. They are
very frequently set up incorrectly, with 3 or 4 gallons of water when
cold. The water will then overflow when the system heats up, and will
take in cold water when it cools down. This will ruin the heating
system in a few years.


John Stumbles April 23rd 05 05:11 PM

Aidan wrote:

Agree, it's a 4 gallon feed and expansion tank for the heating. If it
has distorted, maybe it's had very hot water in it when the heating was
running; this would indicate a fault. It should always be cold.


You probably need to replace the washer in the float valve/ballcock. It
should have about 1" or 2" of water covering the outlet when the
heating system is cold, leaving about 3 gallons of airspace to
accomodate the expansion of the water when the system is hot. They are
very frequently set up incorrectly, with 3 or 4 gallons of water when
cold. The water will then overflow when the system heats up, and will
take in cold water when it cools down. This will ruin the heating
system in a few years.


What can also happen if the vent pipe (upside down U shaped pipe with open
end over the tank) is too close to the water level is that water can
continously pump over from the vent pipe into the header tank which then
gets heated up to the temperature of water from the boiler. The plastic
float valve may then burst and let in water as the system cools down, so it
no longer floats and so the float valve opens and lets water in to the tank
until it flows out of the overflow: this also raises the water level in the
tank encouraging pumping over to continue.

Sometimes the vent pipe is supposed to be fixed to something and has come
loose. It should stop just below the rim of the tank, so that it's well
above the water level. It should also go up 6" or so above the level of the
open end.

As Aidan says the water level in the tank should be quite low when the
system is cold, maybe 3" (it will rise when the system heats up and the
water expands). To maintain this level the brass rod on the float valve
will usually have to be bent down.




All times are GMT +1. The time now is 10:05 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004 - 2014 DIYbanter