ReWind the Transformer
Some years (10+) back I partially unwound the power transformer for my
power supply on the Hurco mill so that I could stay within the safe margins for the servo drivers I chose. Sadly the servo drivers did not hold up. I replaced them with same more than once before finally upgrading to something that could handle a lot more. I've got one servo motor that is getting pretty hot. Its also got the most load on the machine. The Y-axis motor. Its a belt drive and it has to sling around the weight of the table and the saddle. It gets hot enough after a few hours to give a 1st degree burn. Not quite enough to make instant skin death, but its hot. You would suffer injury if you wrapped your hand around it and held on. I have considered a couple options including converting it from a belt drive to a direct drive. A direct drive would have much less parasitic load. There may be an issue with the ballscrew itself, but I'm holding out. I have loosened the gibbs slightly, and I have made sure the ball nut and the gibbs are getting plenty of oil from the automatic oiler. I am wondering if I increase the voltage by rewinding a few wraps back onto the transformer to bump the voltage back up to the original 90(+/-) VDC instead of the current 78VDC. If the voltage is higher the current should be lower at the same load requirements. Will that result (within reasonable limits) in a slightly cooler motor? I'm also considering wrapping a heat sink around the body of the motor with a generous slathering of heat sink compound. I believe I can make a bendable heat sink that could be warped to fit the motor. In all the years I have owned this machine i have always had issues with the Y axis. Its burned up servo drives, and a while back the motor cooked. I do mean cooked. Actually I am considering doing all of the above. My only real issue with any of these things is that making the axis direct drive will result in that huge motor (and protective cover) sticking out in front of the machine in the way of daily operation. |
#2
Posted to rec.crafts.metalworking
|
|||
|
|||
ReWind the Transformer
On Thu, 10 Oct 2019 10:29:22 -0700, Bob La Londe wrote:
Some years (10+) back I partially unwound the power transformer for my power supply on the Hurco mill so that I could stay within the safe margins for the servo drivers I chose. Sadly the servo drivers did not hold up. I replaced them with same more than once before finally upgrading to something that could handle a lot more. I've got one servo motor that is getting pretty hot. Its also got the most load on the machine. The Y-axis motor. Its a belt drive and it has to sling around the weight of the table and the saddle. It gets hot enough after a few hours to give a 1st degree burn. Not quite enough to make instant skin death, but its hot. You would suffer injury if you wrapped your hand around it and held on. This is a horizontal mill? The Y axis is vertical? Does it have a counterweight or air spring to coutner the weight of the table? That would be the first thing I'd consider. I have considered a couple options including converting it from a belt drive to a direct drive. A direct drive would have much less parasitic load. I really doubt the belt makes any difference. There may be an issue with the ballscrew itself, but I'm holding out. I have loosened the gibbs slightly, and I have made sure the ball nut and the gibbs are getting plenty of oil from the automatic oiler. I am wondering if I increase the voltage by rewinding a few wraps back onto the transformer to bump the voltage back up to the original 90(+/-) VDC instead of the current 78VDC. If the voltage is higher the current should be lower at the same load requirements. Will that result (within reasonable limits) in a slightly cooler motor? No, it will make no difference. The drive gives the motor the current required to deliver the torque needed to stay in position. Higher voltage to the drive MIGHT actually make it worse. I'm also considering wrapping a heat sink around the body of the motor with a generous slathering of heat sink compound. I believe I can make a bendable heat sink that could be warped to fit the motor. If this is a DC brush motor, that will have little benefit. It is the rotor (armature) that is producing all the heat. Possibly forced air cooling to the motor will help. If it is a brushless motor, then heat sinks of forced air cooling will help a lot, as all the hear is generated in the stator. In all the years I have owned this machine i have always had issues with the Y axis. Its burned up servo drives, and a while back the motor cooked. I do mean cooked. And, if you can't hold your hand on it, then you are COOKING it now! Jon |
#3
Posted to rec.crafts.metalworking
|
|||
|
|||
ReWind the Transformer
On 10/10/2019 11:34 AM, Jon Elson wrote: On Thu, 10 Oct 2019 10:29:22
-0700, Bob La Londe wrote: Some years (10+) back I partially unwound the power transformer for my power supply on the Hurco mill so that I could stay within the safe margins for the servo drivers I chose. Sadly the servo drivers did not hold up. I replaced them with same more than once before finally upgrading to something that could handle a lot more. I've got one servo motor that is getting pretty hot. Its also got the most load on the machine. The Y-axis motor. Its a belt drive and it has to sling around the weight of the table and the saddle. It gets hot enough after a few hours to give a 1st degree burn. Not quite enough to make instant skin death, but its hot. You would suffer injury if you wrapped your hand around it and held on. This is a horizontal mill? The Y axis is vertical? Does it have a counterweight or air spring to coutner the weight of the table? No, no, and no. I'd guess that table and saddle at around 1000 lbs. Conventional XY movement. That would be the first thing I'd consider. I have considered a couple options including converting it from a belt drive to a direct drive. A direct drive would have much less parasitic load. I really doubt the belt makes any difference. Any? mechanical power transmission always has some associated loss in usable power. The timing belts on this machine are pretty darned tight. I matched the deflection on the Y up with the deflection on the Z. They are the same center to center distance, and the Z has no issues. There may be an issue with the ballscrew itself, but I'm holding out. I have loosened the gibbs slightly, and I have made sure the ball nut and the gibbs are getting plenty of oil from the automatic oiler. I am wondering if I increase the voltage by rewinding a few wraps back onto the transformer to bump the voltage back up to the original 90(+/-) VDC instead of the current 78VDC. If the voltage is higher the current should be lower at the same load requirements. Will that result (within reasonable limits) in a slightly cooler motor? No, it will make no difference. The drive gives the motor the current required to deliver the torque needed to stay in position. Higher voltage to the drive MIGHT actually make it worse. I considered there might be an issue with back EMF at higher voltage, but generically total power is a function of amps*volts. Its my understanding that DC motors typically have a sweet spot, and it was originally powered at 90VDC. My thought was in addition to requiring maybe less current for operation it might also be its "sweet spot." I'm also considering wrapping a heat sink around the body of the motor with a generous slathering of heat sink compound. I believe I can make a bendable heat sink that could be warped to fit the motor. If this is a DC brush motor, that will have little benefit. It is the rotor (armature) that is producing all the heat. Possibly forced air cooling to the motor will help. If it is a brushless motor, then heat sinks of forced air cooling will help a lot, as all the hear is generated in the stator. Do you think the heat might have an affect on the field of the permanent magnets? Its not an open motor, so forced air through the motor is not an option. Of course air could be blown over the motor, but that would not directly cool the rotor. In all the years I have owned this machine i have always had issues with the Y axis. Its burned up servo drives, and a while back the motor cooked. I do mean cooked. And, if you can't hold your hand on it, then you are COOKING it now! I am aware. |
#4
Posted to rec.crafts.metalworking
|
|||
|
|||
ReWind the Transformer
On Thu, 10 Oct 2019 13:11:46 -0700, Bob La Londe
wrote: On 10/10/2019 11:34 AM, Jon Elson wrote: On Thu, 10 Oct 2019 10:29:22 -0700, Bob La Londe wrote: Some years (10+) back I partially unwound the power transformer for my power supply on the Hurco mill so that I could stay within the safe margins for the servo drivers I chose. Sadly the servo drivers did not hold up. I replaced them with same more than once before finally upgrading to something that could handle a lot more. I've got one servo motor that is getting pretty hot. Its also got the most load on the machine. The Y-axis motor. Its a belt drive and it has to sling around the weight of the table and the saddle. It gets hot enough after a few hours to give a 1st degree burn. Not quite enough to make instant skin death, but its hot. You would suffer injury if you wrapped your hand around it and held on. This is a horizontal mill? The Y axis is vertical? Does it have a counterweight or air spring to coutner the weight of the table? No, no, and no. I'd guess that table and saddle at around 1000 lbs. Conventional XY movement. That would be the first thing I'd consider. I have considered a couple options including converting it from a belt drive to a direct drive. A direct drive would have much less parasitic load. I really doubt the belt makes any difference. Any? mechanical power transmission always has some associated loss in usable power. The timing belts on this machine are pretty darned tight. I matched the deflection on the Y up with the deflection on the Z. They are the same center to center distance, and the Z has no issues. There may be an issue with the ballscrew itself, but I'm holding out. I have loosened the gibbs slightly, and I have made sure the ball nut and the gibbs are getting plenty of oil from the automatic oiler. I am wondering if I increase the voltage by rewinding a few wraps back onto the transformer to bump the voltage back up to the original 90(+/-) VDC instead of the current 78VDC. If the voltage is higher the current should be lower at the same load requirements. Will that result (within reasonable limits) in a slightly cooler motor? No, it will make no difference. The drive gives the motor the current required to deliver the torque needed to stay in position. Higher voltage to the drive MIGHT actually make it worse. I considered there might be an issue with back EMF at higher voltage, but generically total power is a function of amps*volts. Its my understanding that DC motors typically have a sweet spot, and it was originally powered at 90VDC. My thought was in addition to requiring maybe less current for operation it might also be its "sweet spot." I'm also considering wrapping a heat sink around the body of the motor with a generous slathering of heat sink compound. I believe I can make a bendable heat sink that could be warped to fit the motor. If this is a DC brush motor, that will have little benefit. It is the rotor (armature) that is producing all the heat. Possibly forced air cooling to the motor will help. If it is a brushless motor, then heat sinks of forced air cooling will help a lot, as all the hear is generated in the stator. Do you think the heat might have an affect on the field of the permanent magnets? Its not an open motor, so forced air through the motor is not an option. Of course air could be blown over the motor, but that would not directly cool the rotor. In all the years I have owned this machine i have always had issues with the Y axis. Its burned up servo drives, and a while back the motor cooked. I do mean cooked. And, if you can't hold your hand on it, then you are COOKING it now! I am aware. Greetings Bob, Your DC brushed motor consumes current based on the torque requirement while the voltage is related to speed. So higher voltage will help it go faster but will not lower the current required. If you could change the torque requirement that would help. Can you change the gearing so that the motor spins faster? Years ago I ran into this exact problem on a home made 4th axis. And the solution was to speed up the motor while lowering the torque. You are correct that total power is voltage times current. Unfortunately supplying more voltage to the motor will not cause it to draw less current. Eric |
#6
Posted to rec.crafts.metalworking
|
|||
|
|||
ReWind the Transformer
On 10/10/2019 2:15 PM, Bob La Londe wrote:
I have been looking for a band-aid (rather than surgery) for this application.Â* I think that might just be the band-aid I need.Â* Right now its a 1:1 belt drive. I will have to think about that some.Â* It would be nice to keep the motor inside the knee where it is now. My bandaid solution would be to clamp a heat sink with fins to the servo. Paul |
#7
Posted to rec.crafts.metalworking
|
|||
|
|||
ReWind the Transformer
Higher voltage means more power but less time. The sweet spot you
mentioned is in there somewhere. Winding the transformer back to normal first will give you an answer of some sort. Hul Bob La Londe wrote: Some years (10+) back I partially unwound the power transformer for my power supply on the Hurco mill so that I could stay within the safe margins for the servo drivers I chose. Sadly the servo drivers did not hold up. I replaced them with same more than once before finally upgrading to something that could handle a lot more. I've got one servo motor that is getting pretty hot. Its also got the most load on the machine. The Y-axis motor. Its a belt drive and it has to sling around the weight of the table and the saddle. It gets hot enough after a few hours to give a 1st degree burn. Not quite enough to make instant skin death, but its hot. You would suffer injury if you wrapped your hand around it and held on. I have considered a couple options including converting it from a belt drive to a direct drive. A direct drive would have much less parasitic load. There may be an issue with the ballscrew itself, but I'm holding out. I have loosened the gibbs slightly, and I have made sure the ball nut and the gibbs are getting plenty of oil from the automatic oiler. I am wondering if I increase the voltage by rewinding a few wraps back onto the transformer to bump the voltage back up to the original 90(+/-) VDC instead of the current 78VDC. If the voltage is higher the current should be lower at the same load requirements. Will that result (within reasonable limits) in a slightly cooler motor? I'm also considering wrapping a heat sink around the body of the motor with a generous slathering of heat sink compound. I believe I can make a bendable heat sink that could be warped to fit the motor. In all the years I have owned this machine i have always had issues with the Y axis. Its burned up servo drives, and a while back the motor cooked. I do mean cooked. Actually I am considering doing all of the above. My only real issue with any of these things is that making the axis direct drive will result in that huge motor (and protective cover) sticking out in front of the machine in the way of daily operation. |
#8
Posted to rec.crafts.metalworking
|
|||
|
|||
ReWind the Transformer
|
#10
Posted to rec.crafts.metalworking
|
|||
|
|||
ReWind the Transformer
On Thursday, October 10, 2019 at 10:29:27 AM UTC-7, Bob La Londe wrote:
Some years (10+) back I partially unwound the power transformer for my power supply on the Hurco mill so that I could stay within the safe margins for the servo drivers I chose. Sadly the servo drivers did not hold up. I replaced them with same more than once before finally upgrading to something that could handle a lot more. I've got one servo motor that is getting pretty hot. Its also got the most load on the machine. The Y-axis motor. Its a belt drive and it has to sling around the weight of the table and the saddle. It gets hot enough after a few hours to give a 1st degree burn. Not quite enough to make instant skin death, but its hot. You would suffer injury if you wrapped your hand around it and held on. I have considered a couple options including converting it from a belt drive to a direct drive. A direct drive would have much less parasitic load. There may be an issue with the ballscrew itself, but I'm holding out. I have loosened the gibbs slightly, and I have made sure the ball nut and the gibbs are getting plenty of oil from the automatic oiler. I am wondering if I increase the voltage by rewinding a few wraps back onto the transformer to bump the voltage back up to the original 90(+/-) VDC instead of the current 78VDC. If the voltage is higher the current should be lower at the same load requirements. Will that result (within reasonable limits) in a slightly cooler motor? I'm also considering wrapping a heat sink around the body of the motor with a generous slathering of heat sink compound. I believe I can make a bendable heat sink that could be warped to fit the motor. In all the years I have owned this machine i have always had issues with the Y axis. Its burned up servo drives, and a while back the motor cooked. I do mean cooked. Actually I am considering doing all of the above. My only real issue with any of these things is that making the axis direct drive will result in that huge motor (and protective cover) sticking out in front of the machine in the way of daily operation. I think changing the motor drive ratio is the best solution. However if one wants to get heat out of a brush dc motor i would get a non contact temperature sensor ($30 at harbor freight) and find the hot spots. The hot spots are the place to apply cooling. If the motor has plain bearing than most of the heat is being rejected though the shaft to the housing. If they are ball bearing then the heat is likely from convection of the air internal to the motor to the housing. If you put a fan on the output shaft that blows over the motor housing you attack to heat sources. You cool the motor shaft and you cool the motor housing with force air which provides much more cooling than a static heat sink. If one need more cooling wrap copper tube around the motor and pass cold water though it. |
#11
Posted to rec.crafts.metalworking
|
|||
|
|||
ReWind the Transformer
On Thu, 10 Oct 2019 13:34:04 -0500, Jon Elson
wrote: On Thu, 10 Oct 2019 10:29:22 -0700, Bob La Londe wrote: Some years (10+) back I partially unwound the power transformer for my power supply on the Hurco mill so that I could stay within the safe margins for the servo drivers I chose. Sadly the servo drivers did not hold up. I replaced them with same more than once before finally upgrading to something that could handle a lot more. I've got one servo motor that is getting pretty hot. Its also got the most load on the machine. The Y-axis motor. Its a belt drive and it has to sling around the weight of the table and the saddle. It gets hot enough after a few hours to give a 1st degree burn. Not quite enough to make instant skin death, but its hot. You would suffer injury if you wrapped your hand around it and held on. This is a horizontal mill? The Y axis is vertical? Does it have a counterweight or air spring to coutner the weight of the table? That would be the first thing I'd consider. I have considered a couple options including converting it from a belt drive to a direct drive. A direct drive would have much less parasitic load. I really doubt the belt makes any difference. There may be an issue with the ballscrew itself, but I'm holding out. I have loosened the gibbs slightly, and I have made sure the ball nut and the gibbs are getting plenty of oil from the automatic oiler. I am wondering if I increase the voltage by rewinding a few wraps back onto the transformer to bump the voltage back up to the original 90(+/-) VDC instead of the current 78VDC. If the voltage is higher the current should be lower at the same load requirements. Will that result (within reasonable limits) in a slightly cooler motor? No, it will make no difference. The drive gives the motor the current required to deliver the torque needed to stay in position. Higher voltage to the drive MIGHT actually make it worse. I'm also considering wrapping a heat sink around the body of the motor with a generous slathering of heat sink compound. I believe I can make a bendable heat sink that could be warped to fit the motor. If this is a DC brush motor, that will have little benefit. It is the rotor (armature) that is producing all the heat. Possibly forced air cooling to the motor will help. If it is a brushless motor, then heat sinks of forced air cooling will help a lot, as all the hear is generated in the stator. In all the years I have owned this machine i have always had issues with the Y axis. Its burned up servo drives, and a while back the motor cooked. I do mean cooked. And, if you can't hold your hand on it, then you are COOKING it now! Jon He can tune the servo amp back a bit. Increasing the power to the servo amp may also be of service. Whats the rating of the servo? Many will run at 90 volts. I do agree..some forced air cooling will definately be of help. Is he sure they are tuned correctly? Gunner __ "Poor widdle Wudy...mentally ill, lies constantly, doesnt know who he is, or even what gender "he" is. No more pathetic creature has ever walked the earth. But...he is locked into a mental hospital for the safety of the public. Which is a very good thing." Asun rauhassa, valmistaudun sotaan. -- This email has been checked for viruses by Avast antivirus software. https://www.avast.com/antivirus |
#12
Posted to rec.crafts.metalworking
|
|||
|
|||
ReWind the Transformer
On Thu, 17 Oct 2019 08:36:03 -0700, Gunner Asch
wrote: On Thu, 10 Oct 2019 13:34:04 -0500, Jon Elson wrote: On Thu, 10 Oct 2019 10:29:22 -0700, Bob La Londe wrote: Some years (10+) back I partially unwound the power transformer for my power supply on the Hurco mill so that I could stay within the safe margins for the servo drivers I chose. Sadly the servo drivers did not hold up. I replaced them with same more than once before finally upgrading to something that could handle a lot more. I've got one servo motor that is getting pretty hot. Its also got the most load on the machine. The Y-axis motor. Its a belt drive and it has to sling around the weight of the table and the saddle. It gets hot enough after a few hours to give a 1st degree burn. Not quite enough to make instant skin death, but its hot. You would suffer injury if you wrapped your hand around it and held on. This is a horizontal mill? The Y axis is vertical? Does it have a counterweight or air spring to coutner the weight of the table? That would be the first thing I'd consider. I have considered a couple options including converting it from a belt drive to a direct drive. A direct drive would have much less parasitic load. I really doubt the belt makes any difference. There may be an issue with the ballscrew itself, but I'm holding out. I have loosened the gibbs slightly, and I have made sure the ball nut and the gibbs are getting plenty of oil from the automatic oiler. I am wondering if I increase the voltage by rewinding a few wraps back onto the transformer to bump the voltage back up to the original 90(+/-) VDC instead of the current 78VDC. If the voltage is higher the current should be lower at the same load requirements. Will that result (within reasonable limits) in a slightly cooler motor? No, it will make no difference. The drive gives the motor the current required to deliver the torque needed to stay in position. Higher voltage to the drive MIGHT actually make it worse. I'm also considering wrapping a heat sink around the body of the motor with a generous slathering of heat sink compound. I believe I can make a bendable heat sink that could be warped to fit the motor. If this is a DC brush motor, that will have little benefit. It is the rotor (armature) that is producing all the heat. Possibly forced air cooling to the motor will help. If it is a brushless motor, then heat sinks of forced air cooling will help a lot, as all the hear is generated in the stator. In all the years I have owned this machine i have always had issues with the Y axis. Its burned up servo drives, and a while back the motor cooked. I do mean cooked. And, if you can't hold your hand on it, then you are COOKING it now! Jon He can tune the servo amp back a bit. Increasing the power to the servo amp may also be of service. Whats the rating of the servo? Many will run at 90 volts. I do agree..some forced air cooling will definately be of help. Is he sure they are tuned correctly? Gunner Damn..I just reread..you are using steppers? Ack! Gunner __ "Poor widdle Wudy...mentally ill, lies constantly, doesnt know who he is, or even what gender "he" is. No more pathetic creature has ever walked the earth. But...he is locked into a mental hospital for the safety of the public. Which is a very good thing." Asun rauhassa, valmistaudun sotaan. __ "Poor widdle Wudy...mentally ill, lies constantly, doesnt know who he is, or even what gender "he" is. No more pathetic creature has ever walked the earth. But...he is locked into a mental hospital for the safety of the public. Which is a very good thing." Asun rauhassa, valmistaudun sotaan. -- This email has been checked for viruses by Avast antivirus software. https://www.avast.com/antivirus |
#13
Posted to rec.crafts.metalworking
|
|||
|
|||
ReWind the Transformer
On Thu, 10 Oct 2019 10:29:22 -0700, Bob La Londe
wrote: Some years (10+) back I partially unwound the power transformer for my power supply on the Hurco mill so that I could stay within the safe margins for the servo drivers I chose. Sadly the servo drivers did not hold up. I replaced them with same more than once before finally upgrading to something that could handle a lot more. I've got one servo motor that is getting pretty hot. Its also got the most load on the machine. The Y-axis motor. Its a belt drive and it has to sling around the weight of the table and the saddle. It gets hot enough after a few hours to give a 1st degree burn. Not quite enough to make instant skin death, but its hot. You would suffer injury if you wrapped your hand around it and held on. I have considered a couple options including converting it from a belt drive to a direct drive. A direct drive would have much less parasitic load. There may be an issue with the ballscrew itself, but I'm holding out. I have loosened the gibbs slightly, and I have made sure the ball nut and the gibbs are getting plenty of oil from the automatic oiler. I am wondering if I increase the voltage by rewinding a few wraps back onto the transformer to bump the voltage back up to the original 90(+/-) VDC instead of the current 78VDC. If the voltage is higher the current should be lower at the same load requirements. Will that result (within reasonable limits) in a slightly cooler motor? I'm also considering wrapping a heat sink around the body of the motor with a generous slathering of heat sink compound. I believe I can make a bendable heat sink that could be warped to fit the motor. In all the years I have owned this machine i have always had issues with the Y axis. Its burned up servo drives, and a while back the motor cooked. I do mean cooked. Actually I am considering doing all of the above. My only real issue with any of these things is that making the axis direct drive will result in that huge motor (and protective cover) sticking out in front of the machine in the way of daily operation. What you loose in a toothed belt drive is barely noise in the grand scheme of things. How about a bigger motor? Changing the voltage is unlikely to help as the POWER dissipation won't change appreciably by raising the volts. So the amps drop a bit - the volt/amps stay the same. I'd be tempted to either add a big finned heat sink or wrap a few turns of copper tubing around it and add a pump and radiator - - - - run glycol like in an automotive cooling system |
#14
Posted to rec.crafts.metalworking
|
|||
|
|||
ReWind the Transformer
On Thu, 10 Oct 2019 13:11:46 -0700, Bob La Londe
wrote: On 10/10/2019 11:34 AM, Jon Elson wrote: On Thu, 10 Oct 2019 10:29:22 -0700, Bob La Londe wrote: Some years (10+) back I partially unwound the power transformer for my power supply on the Hurco mill so that I could stay within the safe margins for the servo drivers I chose. Sadly the servo drivers did not hold up. I replaced them with same more than once before finally upgrading to something that could handle a lot more. I've got one servo motor that is getting pretty hot. Its also got the most load on the machine. The Y-axis motor. Its a belt drive and it has to sling around the weight of the table and the saddle. It gets hot enough after a few hours to give a 1st degree burn. Not quite enough to make instant skin death, but its hot. You would suffer injury if you wrapped your hand around it and held on. This is a horizontal mill? The Y axis is vertical? Does it have a counterweight or air spring to coutner the weight of the table? No, no, and no. I'd guess that table and saddle at around 1000 lbs. Conventional XY movement. That would be the first thing I'd consider. I have considered a couple options including converting it from a belt drive to a direct drive. A direct drive would have much less parasitic load. I really doubt the belt makes any difference. Any? mechanical power transmission always has some associated loss in usable power. The timing belts on this machine are pretty darned tight. I matched the deflection on the Y up with the deflection on the Z. They are the same center to center distance, and the Z has no issues. There may be an issue with the ballscrew itself, but I'm holding out. I have loosened the gibbs slightly, and I have made sure the ball nut and the gibbs are getting plenty of oil from the automatic oiler. I am wondering if I increase the voltage by rewinding a few wraps back onto the transformer to bump the voltage back up to the original 90(+/-) VDC instead of the current 78VDC. If the voltage is higher the current should be lower at the same load requirements. Will that result (within reasonable limits) in a slightly cooler motor? No, it will make no difference. The drive gives the motor the current required to deliver the torque needed to stay in position. Higher voltage to the drive MIGHT actually make it worse. I considered there might be an issue with back EMF at higher voltage, but generically total power is a function of amps*volts. Its my understanding that DC motors typically have a sweet spot, and it was originally powered at 90VDC. My thought was in addition to requiring maybe less current for operation it might also be its "sweet spot." I'm also considering wrapping a heat sink around the body of the motor with a generous slathering of heat sink compound. I believe I can make a bendable heat sink that could be warped to fit the motor. If this is a DC brush motor, that will have little benefit. It is the rotor (armature) that is producing all the heat. Possibly forced air cooling to the motor will help. If it is a brushless motor, then heat sinks of forced air cooling will help a lot, as all the hear is generated in the stator. Do you think the heat might have an affect on the field of the permanent magnets? Its not an open motor, so forced air through the motor is not an option. Of course air could be blown over the motor, but that would not directly cool the rotor. In all the years I have owned this machine i have always had issues with the Y axis. Its burned up servo drives, and a while back the motor cooked. I do mean cooked. And, if you can't hold your hand on it, then you are COOKING it now! I am aware. Sounds like you are sending a boy to do a man's job. Either change the ratio or put a bigger motor on it. |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
how can tape loop in cassette if i dont have rewind? | Electronics Repair | |||
hlv hardinge carriage motor rewind uk model | Metalworking | |||
Briggs and Stratton 5 hp Starter Rewind Problem | Home Repair | |||
JVC VHS deck won't rewind/eject tape without chewing on it a little | Electronics Repair | |||
Rewind problem with Philips AC/DC Combo Unit | Electronics Repair |