Home |
Search |
Today's Posts |
|
Home Repair (alt.home.repair) For all homeowners and DIYers with many experienced tradesmen. Solve your toughest home fix-it problems. |
Reply |
|
LinkBack | Thread Tools | Display Modes |
#1
|
|||
|
|||
Venting bathroom fan to ridge vent - is it ok?
I live in a one story house with an unfinished attic. Currently, the
bathroom fan is vented by a 3" PVC duct that passes through the attic and out the roof. The attic gets cold (blown in rock-wool insulation lays between the foor joists) and the humid air being vented from the bathroom condenses. Unfortunately, the PVC is sloped the wrong way so condensate is dripping back through the fan and into the bathroom. Messy, and damage to the bathroom ceiling is occurring. I'm planning to replace the fan with a quieter one with more volume, and I'd really like to avoid having to put another hole in the roof, and I also don't want to use the present ducting. A builder who helped with some other renovations has told me that it's ok to run the fan exhaust duct (it'll be 4" diam) up to just beneath the ridge vent, and to allow the exhaust to vent through the ridge vent. Is this likely to work, and is it an acceptable way of venting? I wonder about blowback and about iceing during the winter. Also, is it reasonable to insulate the exhaust ducting to minimize condensation within it? Thanks for any comments or suggestions. Bill Christens-Barry -- Wm A Christens-Barry, PhD Equipoise Imaging, LLC http://www.eqpi.net/eqpi/ |
#2
|
|||
|
|||
"Bill Christens-Barry" wrote in message ... I live in a one story house with an unfinished attic. Currently, the bathroom fan is vented by a 3" PVC duct that passes through the attic and out the roof. The attic gets cold (blown in rock-wool insulation lays between the foor joists) and the humid air being vented from the bathroom condenses. Unfortunately, the PVC is sloped the wrong way so condensate is dripping back through the fan and into the bathroom. Messy, and damage to the bathroom ceiling is occurring. I'm planning to replace the fan with a quieter one with more volume, and I'd really like to avoid having to put another hole in the roof, and I also don't want to use the present ducting. A builder who helped with some other renovations has told me that it's ok to run the fan exhaust duct (it'll be 4" diam) up to just beneath the ridge vent, and to allow the exhaust to vent through the ridge vent. Is this likely to work, and is it an acceptable way of venting? I wonder about blowback and about iceing during the winter. Also, is it reasonable to insulate the exhaust ducting to minimize condensation within it? Thanks for any comments or suggestions. Bill Christens-Barry -- Wm A Christens-Barry, PhD Equipoise Imaging, LLC http://www.eqpi.net/eqpi/ This is a question for you local building authority. Personally I would consider using the old pvc and insulate it. I would not want a fart fan venting into the attic, cause around here that is not acceptable. Hence the roof penetrations. Your going to have some problems with the 3 inch pipe. Everything I have seen recently is 4 inch or larger. alternate solution vent to the eves. |
#3
|
|||
|
|||
Bill Christens-Barry wrote:
I live in a one story house with an unfinished attic. Currently, the bathroom fan is vented by a 3" PVC duct that passes through the attic and out the roof. The attic gets cold (blown in rock-wool insulation lays between the foor joists) and the humid air being vented from the bathroom condenses. Unfortunately, the PVC is sloped the wrong way so condensate is dripping back through the fan and into the bathroom. Messy, and damage to the bathroom ceiling is occurring. I'm planning to replace the fan with a quieter one with more volume, and I'd really like to avoid having to put another hole in the roof, and I also don't want to use the present ducting. A builder who helped with some other renovations has told me that it's ok to run the fan exhaust duct (it'll be 4" diam) up to just beneath the ridge vent, and to allow the exhaust to vent through the ridge vent. Is this likely to work, and is it an acceptable way of venting? I wonder about blowback and about iceing during the winter. Also, is it reasonable to insulate the exhaust ducting to minimize condensation within it? Thanks for any comments or suggestions. Bill Christens-Barry It get's done that way, but it is a very poor idea. I am guessing you are talking about eave vent which is what many do. Most of the warm moist air just ends up in the attic causing trouble. If it is the ridge (top of the roof) that may be better, but again there will be more warm most air in your attic that should be there. Do it right and put it through the roof. -- Joseph Meehan 26 + 6 = 1 It's Irish Math |
#4
|
|||
|
|||
If you get condensation in the exhaust duct now, I expect you'll get
condensation in your attic if you vent it within the attic, even at the ridge vent. That's bad -- not just ice in winter, but water that promotes rot and mold. -- is Joshua Putnam http://www.phred.org/~josh/ Books for Bicycle Mechanics and Tinkerers: http://www.phred.org/~josh/bike/bikebooks.html |
#5
|
|||
|
|||
Vent it to the eve's, where there is a vent,If you go to the ridge(peak)
won't the condensation still run down the tube into the bathroom, had mine that way (eve) for 11 yrs, just replaced the fan in the bath this weekend, covered the 4" tube with extra insulation. I installed a 130cfm, Nataluis $99. Tom "Bill Christens-Barry" wrote in message ... I live in a one story house with an unfinished attic. Currently, the bathroom fan is vented by a 3" PVC duct that passes through the attic and out the roof. The attic gets cold (blown in rock-wool insulation lays between the foor joists) and the humid air being vented from the bathroom condenses. Unfortunately, the PVC is sloped the wrong way so condensate is dripping back through the fan and into the bathroom. Messy, and damage to the bathroom ceiling is occurring. I'm planning to replace the fan with a quieter one with more volume, and I'd really like to avoid having to put another hole in the roof, and I also don't want to use the present ducting. A builder who helped with some other renovations has told me that it's ok to run the fan exhaust duct (it'll be 4" diam) up to just beneath the ridge vent, and to allow the exhaust to vent through the ridge vent. Is this likely to work, and is it an acceptable way of venting? I wonder about blowback and about iceing during the winter. Also, is it reasonable to insulate the exhaust ducting to minimize condensation within it? Thanks for any comments or suggestions. Bill Christens-Barry -- Wm A Christens-Barry, PhD Equipoise Imaging, LLC http://www.eqpi.net/eqpi/ |
#6
|
|||
|
|||
Just inslate the existing pvc pipe in the attic
|
#7
|
|||
|
|||
twfsa wrote:
Vent it to the eve's, where there is a vent, And some will go out the vent and some will go into the attic and make trouble. Even some that does go out will come right back in. The normal air flow is IN the eaves and OUT the high vents. If you go to the ridge(peak) won't the condensation still run down the tube into the bathroom, had mine that way (eve) for 11 yrs, just replaced the fan in the bath this weekend, covered the 4" tube with extra insulation. I installed a 130cfm, Nataluis $99. Tom "Bill Christens-Barry" wrote in message ... I live in a one story house with an unfinished attic. Currently, the bathroom fan is vented by a 3" PVC duct that passes through the attic and out the roof. The attic gets cold (blown in rock-wool insulation lays between the foor joists) and the humid air being vented from the bathroom condenses. Unfortunately, the PVC is sloped the wrong way so condensate is dripping back through the fan and into the bathroom. Messy, and damage to the bathroom ceiling is occurring. I'm planning to replace the fan with a quieter one with more volume, and I'd really like to avoid having to put another hole in the roof, and I also don't want to use the present ducting. A builder who helped with some other renovations has told me that it's ok to run the fan exhaust duct (it'll be 4" diam) up to just beneath the ridge vent, and to allow the exhaust to vent through the ridge vent. Is this likely to work, and is it an acceptable way of venting? I wonder about blowback and about iceing during the winter. Also, is it reasonable to insulate the exhaust ducting to minimize condensation within it? Thanks for any comments or suggestions. Bill Christens-Barry -- Wm A Christens-Barry, PhD Equipoise Imaging, LLC http://www.eqpi.net/eqpi/ -- Joseph Meehan 26 + 6 = 1 It's Irish Math |
#8
|
|||
|
|||
Vent it to the eve's, where there is a vent,
Joseph is right, some of the moisture from the bath fan can get sucked back into the attic through the eave vents. I'm planning to replace the fan with a quieter one with more volume I can highly recommend Panasonic fans. They use squirrel cage fans and are VERY quiet. We have three in our house and are quite happy with them. I'd really like to avoid having to put another hole in the roof I tried to minimize roof penetrations in our house too. We only have two, a large plumbing vent pipe and the woodstove chimney. Our bath fans get ducted through the attic and exit out through gable end walls. It's a slightly longer run, but they do not penetrate the roof and the exhausted moisture isn't anywhere near an eave vent to get sucked back into the house. is it reasonable to insulate the exhaust ducting to minimize condensation within it? Yes, and slope the ducting towards the exterior vent so any condensation can drain away. Best to use rigid ducting like PVC rather than those flexible corrogated things. In our case, the ducting runs through a heated area, but I would insulate the ducts otherwise. Anthony |
#9
Posted to alt.home.repair
|
|||
|
|||
Venting bathroom fan to ridge vent - is it ok?
replying to SQLit, venter wrote:
venting to the eves is one of the worst ideas in the world. eves bring air in which is completley counter prouductive -- for full context, visit https://www.homeownershub.com/mainte...ok-581636-.htm |
#10
Posted to alt.home.repair
|
|||
|
|||
Venting bathroom fan to ridge vent - is it ok?
On Tuesday, May 15, 2018 at 10:14:06 PM UTC-5, venter wrote:
replying to SQLit, venter wrote: venting to the eves is one of the worst ideas in the world. eves bring air in which is completley counter prouductive -- You're too late, 13 YEARS AGO, SQLit died of fart gas poisoning. He never properly vented his bathroom. It was a real tragedy. His gerbils really miss him. 8-( [8~{} Uncle Sad Monster |
#11
Posted to alt.home.repair
|
|||
|
|||
Venting bathroom fan to ridge vent - is it ok?
In alt.home.repair, on Wed, 16 May 2018 03:14:02 GMT, venter
m wrote: replying to SQLit, venter wrote: venting to the eves is one of the worst ideas in the world. eves bring air in which is completley counter prouductive The subject line is about venting to the ridge vent, not the eaves. My house has that. I never use the bathroom fans so I don't know how well the exhaust works, but I don't get any air coming in either. |
#12
Posted to alt.home.repair
|
|||
|
|||
Venting bathroom fan to ridge vent - is it ok?
replying to HerHusband, CarolinaMike wrote:
I was looking for a solution to bathroom venting without penetrating my new roof. The roofer recommended soffit venting, but I feared moisture coming back into the attic. Gable venting makes the most sense and I thank you for the solution. A little slope and probably a dryer vent cover with flap. Makes sense to me. Thanks. -- for full context, visit https://www.homeownershub.com/mainte...ok-581636-.htm |
#13
Posted to alt.home.repair
|
|||
|
|||
Venting bathroom fan to ridge vent - is it ok?
On Saturday, April 20, 2019 at 4:44:05 PM UTC-4, CarolinaMike wrote:
replying to HerHusband, CarolinaMike wrote: I was looking for a solution to bathroom venting without penetrating my new roof. The roofer recommended soffit venting, but I feared moisture coming back into the attic. Gable venting makes the most sense and I thank you for the solution. A little slope and probably a dryer vent cover with flap. Makes sense to me. Thanks. -- for full context, visit https://www.homeownershub.com/mainte...ok-581636-.htm What's the issue with penetrating the roof? As long as it's done correctly there is no issue. And with new shingles it's even less of an issue, it's very simple. Of course it would have been better to resolve all roof issues before the shingle job. |
#14
Posted to alt.home.repair
|
|||
|
|||
Venting bathroom fan to ridge vent - is it ok?
replying to CarolinaMike, Bobby wrote:
Soffit vent works well. How would moisture get back in the attic? It blows down and had a check valve to prevent backflow. -- for full context, visit https://www.homeownershub.com/mainte...ok-581636-.htm |
#15
Posted to alt.home.repair
|
|||
|
|||
Venting bathroom fan to ridge vent - is it ok?
On 2019-04-21 12:14 p.m., Bobby wrote:
replying to CarolinaMike, Bobby wrote: Soffit vent works well.Â* How would moisture get back in the attic?Â* It blows down and had a check valve to prevent backflow. soffit vented , lol |
#16
Posted to alt.home.repair
|
|||
|
|||
Venting bathroom fan to ridge vent - is it ok?
On Sunday, April 21, 2019 at 3:14:06 PM UTC-4, Bobby wrote:
replying to CarolinaMike, Bobby wrote: Soffit vent works well. How would moisture get back in the attic? It blows down and had a check valve to prevent backflow. -- for full context, visit https://www.homeownershub.com/mainte...ok-581636-.htm The soffits are or should be vented to allow air into the attic. Cooler air goes in there and exits via a ridge vent or similar at the peak to ventilate the attic. So, if the bathroom vent is pumping out air, it's not hard to imagine that some of it will wind up going into the attic. Is it the worst thing, that could create a problem? I doubt it. But it might not be allowed by current code either, IDK. |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
Venting bathroom exhaust fans into soffit | Home Repair | |||
Ridge Vent Instalation Question | Home Repair | |||
Bathroom Vent Under Soffet - Not working. ? | Home Repair |