Default Need some help with oil burner not heating 1/2 the house...

Greetings ~

I have a Weil-McLein Gold oil burner and a forced hot water system
feeling 7 radiators in a 2 story colonial.

At the end of last year sthe radiators in question started acting up,
and the start of this year is no different.

So after bleeding all the radiators, having a tune-up with the tech
telling me everything is functioning alright, I start to get
aggravated. Some are blazing hot, others are just luke warm.

So today I check the burner itself at the pipes leading to the
radiators...And I notice that the lower pipe off the burner is not
getting as hot as the top pipe. Top and bottom pipe each lead to 1/2
the radiators in the house.

The bottom pipe has two valves, a big red one in line and a small blue
one that appears to be a run off valve as there is an opeing attached
to it.

The Red valve is twisted hard right, tightened - since I figure it
can't hurt, I go the other way, loosening it to the left...Now the heat
is better, but not blazing.

Now here is my question - could something this simple be the fix, and
if so, why did the tech tighten it in the 1st place???


Bluesman

  #2   Report Post  
m Ransley
 
Posts: n/a
Default

You said lower pipe and top pipe, do you mean the pipes off the boiler,
well one is cold return one is hot supply and of course both valves
should never be closed. Does your recirculator pump run. Is your system
filled, to what lb. Did you bleed radiators, are radiator valves open

  #3   Report Post  
RBM
 
Posts: n/a
Default

I think the big red one you describe, is a flowcheck, which prevents water
from being siphoned from one zone to another. you'd need to be more clear
about the controls on the system, such as zone valves and circulators to
determine what could be causing this
wrote in message
ups.com...
Greetings ~

I have a Weil-McLein Gold oil burner and a forced hot water system
feeling 7 radiators in a 2 story colonial.

At the end of last year sthe radiators in question started acting up,
and the start of this year is no different.

So after bleeding all the radiators, having a tune-up with the tech
telling me everything is functioning alright, I start to get
aggravated. Some are blazing hot, others are just luke warm.

So today I check the burner itself at the pipes leading to the
radiators...And I notice that the lower pipe off the burner is not
getting as hot as the top pipe. Top and bottom pipe each lead to 1/2
the radiators in the house.

The bottom pipe has two valves, a big red one in line and a small blue
one that appears to be a run off valve as there is an opeing attached
to it.

The Red valve is twisted hard right, tightened - since I figure it
can't hurt, I go the other way, loosening it to the left...Now the heat
is better, but not blazing.

Now here is my question - could something this simple be the fix, and
if so, why did the tech tighten it in the 1st place???


Bluesman



Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
more fun with air conditioning J Jensen Home Repair 93 September 7th 04 11:39 AM
more fun with air conditioning J Jensen Home Ownership 56 September 7th 04 07:20 AM
Pool water in central heating system Andy Hall UK diy 1 September 2nd 03 06:01 PM


All times are GMT +1. The time now is 02:28 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"