Baseboard not heating up even after bleeding the line.
I have hydronic heat system at home. One zone. Boiler in basement with 1-1/4" diameter main loop around the basement ceiling perimeter, with a set of venturis and Tees going to each baseboard upstairs and even to the 2nd floor. Each branch from main loop is 1/2" diameter. Every unit works well, except one baseboard unit on 2nd floor doesn't heat up. When i bleed the one bleed valve on it, water immediately comes out. So, no apparent air lock in the pipes. I'm at a loss as to what else it could be. The system has performed perfectly for years. Suggestions appreciated.
Thanks Theodore |
#2
Posted to alt.home.repair
|
|||
|
|||
Baseboard not heating up even after bleeding the line.
|
#3
Posted to alt.home.repair
|
|||
|
|||
Baseboard not heating up even after bleeding the line.
On Sunday, December 22, 2019 at 5:12:17 PM UTC-5, wrote:
I have hydronic heat system at home. One zone. Boiler in basement with 1-1/4" diameter main loop around the basement ceiling perimeter, with a set of venturis and Tees going to each baseboard upstairs and even to the 2nd floor. Each branch from main loop is 1/2" diameter. Every unit works well, except one baseboard unit on 2nd floor doesn't heat up. When i bleed the one bleed valve on it, water immediately comes out. So, no apparent air lock in the pipes. I'm at a loss as to what else it could be. The system has performed perfectly for years. Suggestions appreciated. Thanks Theodore It would seem to indicate that there is a blockage in that one that's preventing water flowing out of it. I assume you bled it for a long time, hot water comes out? |
#4
Posted to alt.home.repair
|
|||
|
|||
Baseboard not heating up even after bleeding the line.
Thank you Micky. Water comes out hot eventually, of course. But it's obviously not circulating through this unit as it does all others. I wonder if it's a clog inside the baseboard, or the Tee, or the Venturi? And what's the best way to diagnose?
|
#5
Posted to alt.home.repair
|
|||
|
|||
Baseboard not heating up even after bleeding the line.
On Sunday, December 22, 2019 at 6:34:00 PM UTC-5, wrote:
Thank you Micky. Water comes out hot eventually, of course. But it's obviously not circulating through this unit as it does all others. I wonder if it's a clog inside the baseboard, or the Tee, or the Venturi? And what's the best way to diagnose? I guess that depends on how it's put together. If there is a union, you can disconnect it see if water will flow through it with a garden hose, snake the pipes, etc. If no unions, then cut we must. I don't see how it can be on the goesinto side, since you get flow through the bleed. Must be on the goesouta side or the radiator. Have an air compressor? How about taking out the bleed fitting or other plug, rigging up some compressed air with a place in the system open so it can blow it out? |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
Hydronic elecric baseboard heater vs standard electric baseboard heater | Home Repair | |||
Radiator cold at top even after bleeding | UK diy | |||
LOUD RADS ?? Central heating Combi boiler Condensing bleeding | UK diy | |||
Celsia multi head heating pump bleeding | UK diy | |||
Bleeding gravity fed heating system | UK diy |