Freezer power needs
Some background ... I am not an expert with electricity, but trying to
learn as much as possible ... .... I just recently moved into a new house and my question(s) is in regards to appliance installation into my unfinished basement. "Lack of power" seems to be prevalent in this case.... 15 amp fuse on breaker, with a 115 volt outlet, labelled for wash machine. The dryer has its own 30 amp breaker and 230 volt outlet. I have a "sump-pump" that has its own 115 volt outlet and a 30 amp breaker nearby as well. I just purchased a small 10 cuft freezer that in the manual is asking for its own seperate circuit at or near 20amps (energy rated at 312kwh); is this power requirement out of line of industry norm? Could I add this to the same outlet as .. say what I currently have my washer on? Or should I call in an expert and have them install another circuit for my freezer? |
#2
|
|||
|
|||
Freezer power needs
|
#3
|
|||
|
|||
Freezer power needs
Couple thoughts come to mind. First, electric motors draw more current than
their labels while they are starting up. So, the big risk is that the freezer and the washer motors are starting up the at the same moment, and trip the fuse. Second thing came to mind, it's not all that dificult for an electrician to put in a new electric socket in an unfinished basement. Probably not all that far away from the electric circuit panel box. -- Christopher A. Young Jesus: The Reason for the Season www.lds.org www.mormons.com "Wade Ekstrom" wrote in message om... Some background ... I am not an expert with electricity, but trying to learn as much as possible ... .... I just recently moved into a new house and my question(s) is in regards to appliance installation into my unfinished basement. "Lack of power" seems to be prevalent in this case.... 15 amp fuse on breaker, with a 115 volt outlet, labelled for wash machine. The dryer has its own 30 amp breaker and 230 volt outlet. I have a "sump-pump" that has its own 115 volt outlet and a 30 amp breaker nearby as well. I just purchased a small 10 cuft freezer that in the manual is asking for its own seperate circuit at or near 20amps (energy rated at 312kwh); is this power requirement out of line of industry norm? Could I add this to the same outlet as .. say what I currently have my washer on? Or should I call in an expert and have them install another circuit for my freezer? |
#4
|
|||
|
|||
Freezer power needs
By national electric code (assuming you are in the us) the washer must
be on its own "Laundry" Circuit. If you have a fairly new panel, with some extra space, it wouldnt be too hard to add mor plugs in the basement. You should also check the sump pump isnt on a 30 amp circuit. If anyone has a sump pump THAT big, the house should be equiped with life preservers : |
#5
|
|||
|
|||
Freezer power needs
If its Yellow Label is 312 KWH than that is less than 1 KWH a day .
Probably it runs at 100 - 150 watt with a max of 3 to 600 on startup. If you really want to know put a clamp on amp meter on it . It sounds like an efficient unit and 15 A is overkill |
#6
|
|||
|
|||
Freezer power needs
Wade Ekstrom wrote: Some background ... I am not an expert with electricity, but trying to learn as much as possible ... ... I just recently moved into a new house and my question(s) is in regards to appliance installation into my unfinished basement. "Lack of power" seems to be prevalent in this case.... 15 amp fuse on breaker, with a 115 volt outlet, labelled for wash machine. The dryer has its own 30 amp breaker and 230 volt outlet. I have a "sump-pump" that has its own 115 volt outlet and a 30 amp breaker nearby as well. I just purchased a small 10 cuft freezer that in the manual is asking for its own seperate circuit at or near 20amps (energy rated at 312kwh); is this power requirement out of line of industry norm? Could I add this to the same outlet as .. say what I currently have my washer on? Or should I call in an expert and have them install another circuit for my freezer? I agree with HaHa. The separate circuit recommendation is for protection from possible food spoilage and has nothing to do with power draw. You can put the freezer on any 15 A circuit (heck you could put 3 of the things on a 15 a circuit); there is no reason for it to be on a 20 A circuit. I have a 17 cubic foot freezer in my garage that is on the same circuit as my tools and lights. The circuit breaker has never tripped even when a 1 hp motor (rated 12.2 a) is running. Recognize that that freezer uses very little power and won't run very often if you keep the door closed and full of frozen food or frozen jugs of water. But, since the basement is unfinished, install another 15 a line just for the freezer if you are worried. |
#7
|
|||
|
|||
Freezer power needs
"Wade Ekstrom" wrote in message Or should I call in an expert and have them install another circuit for my freezer? Just to pile on the other answers, yes, it is a good idea. While he is there, have one or two more circuits and a half dozen receptacles installed. The freeze can share a circuit with another small appliance, but they as for separate ones so if your kids trip out the breaker playing with something and don't tell you, the freezer will not be out also. Now that you have plenty of electric, make a little workbench, get a few power tools, etc. Ed http://pages.cthome.net/edhome |
#8
|
|||
|
|||
Freezer power needs
|
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
Sony KV-2782R and 2785R, power supply problems. | Electronics Repair | |||
Sony KV-2782R Power supply, and KV-2785R same. | Electronics Repair | |||
Power tools in Europe (long) | Woodworking | |||
more info RCA TV CTC169(BG5) Wont come out of standby - Ticking sound when Power button is pressed | Electronics Repair | |||
power flushing | UK diy |