Two questions about closed cell foam inuslation
I've heard about all the advantages, but:
1. Could it be so heavy that it jeopardizes the stability of the roof in a roofline application? 2. The gas that it traps inside - I'm sure it slowly leaks over time - what type of gas is it and is it dangerous? Thanks in advance, Aaron |
#2
Posted to alt.home.repair
|
|||
|
|||
Two questions about closed cell foam inuslation
On Jun 22, 10:45*pm, Aaron Fude wrote:
I've heard about all the advantages, but: 1. Could it be so heavy that it jeopardizes the stability of the roof in a roofline application? Could it? If by that you mean "is it possible to add such a huge weight of foam that it would jeopardize the structure." Yes. But that is an extremely remote possibility. The stuff ain't free. 2. The gas that it traps inside - I'm sure it slowly leaks over time - what type of gas is it and is it dangerous? Are liquids poisonous? There are a number of different foams. DAGS: closed cell foam off gassing R |
#3
Posted to alt.home.repair
|
|||
|
|||
Two questions about closed cell foam inuslation
On Jun 22, 9:45*pm, Aaron Fude wrote:
I've heard about all the advantages, but: 1. Could it be so heavy that it jeopardizes the stability of the roof in a roofline application? 2. The gas that it traps inside - I'm sure it slowly leaks over time - what type of gas is it and is it dangerous? Thanks in advance, Aaron This is for a heated room underneath, right. Its very light it might equal 1/2" of snow, I am guessing, my roof might take 2ft+ load no problem. Some foams off gas little, some more, but the roof will breath it out. In sun in a hot area the roof temp will go up, roof life depending on type, may go down. |
#4
Posted to alt.home.repair
|
|||
|
|||
Two questions about closed cell foam inuslation
|
#5
Posted to alt.home.repair
|
|||
|
|||
Two questions about closed cell foam inuslation
On Jun 23, 11:31*am, Reno wrote:
Aaron Fude wrote in news: I've heard about all the advantages, but: 1. Could it be so heavy that it jeopardizes the stability of the roof in a roofline application? The heaviest foams are about 2 lb per sq ft while roofs are supposed to be designed for loads from 25 to over 50 lbs per sq ft. So the foam won't overload your roof. A square foot is an area, weights are measured by volume. You are also making assumptions about the theoretical roof, such as that it was properly designed to begin with, that there have been no modifications (reroofing, truss chords cut), etc. 2. The gas that it traps inside - I'm sure it slowly leaks over time - what type of gas is it and is it dangerous? There are many different chemicals used for the foams but a good guess would be that the foams could off-gas. These foams are used in many houses so if you use one of the better known brands you would be safe. If this is intended to be a living space you could get additional gas proofing by using a vapor barrier over the foam. If it ia an open attis area then the normal ventilation should prevent gas build up. Polyethylene is the standard vapor barrier used in residential construction. It is intended to drastically reduce water vapor transmission, not gas transmission. I do not know the gas permeability performance of polyethylene off hand, but it appears that you are making another assumption. R |
#6
Posted to alt.home.repair
|
|||
|
|||
Two questions about closed cell foam inuslation
On 2009-06-23, Aaron Fude wrote:
1. Could it be so heavy that it jeopardizes the stability of the roof in a roofline application? Typical closed cell polyurethane foam insulation has a density around 2 lbs per cubic foot. [For exposed roof applications, where the foam is the finished roof, the density can be higher.] So if you were to spray it 6 inches deep, which is a lot of foam, that would be 1 lb per square foot. By contrast, a typical design dead load would be 10 lbs per square foot, and a design roof live load would be 20 lbs per square foot, higher in areas with heavy snow. 2. The gas that it traps inside - I'm sure it slowly leaks over time - what type of gas is it and is it dangerous? The gas is called a blowing agent, you could try searching on that to see what information you get. It does slowly leak out over time, which is part of the reason there is some small degradation in R value over time. Cheers, Wayne |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
Closed Cell Foam Insulation... | Home Repair | |||
Can I switch the sim in my damaged Cell Phone to a new Cell Phone? | Electronics Repair | |||
Carpet Pad: Memory foam versus non-memory foam? | Home Repair | |||
Decent cell phone headset & plug adaptation questions | Electronics Repair | |||
Questions on weight-closed fencegate | Woodworking |