  #1   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 91
Default crimped versus wirenutted grounds?

I replaced an outlet today at a commercial site. Now I admit I don't know
anything about commercial electrical, but around here grounds are required
to be crimped residentially; wirenutting isn't allowed.

I was surprised to see the ground was wirenutted. I assume that if crimping
is required for residential, it would also be required for commercial.

Is that likely to be a valid assumption or not?


  #2   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,563
Default crimped versus wirenutted grounds?


"jack" wrote in message
...
I replaced an outlet today at a commercial site. Now I admit I don't know
anything about commercial electrical, but around here grounds are required
to be crimped residentially; wirenutting isn't allowed.

I was surprised to see the ground was wirenutted. I assume that if
crimping is required for residential, it would also be required for
commercial.

Is that likely to be a valid assumption or not?


You must be in a place that doesn't follow the NEC, therefore you need to
follow whatever rules that place uses




  #3   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,934
Default crimped versus wirenutted grounds?


"jack" wrote in message
...
I replaced an outlet today at a commercial site. Now I admit I don't know
anything about commercial electrical, but around here grounds are required
to be crimped residentially; wirenutting isn't allowed.

I was surprised to see the ground was wirenutted. I assume that if
crimping is required for residential, it would also be required for
commercial.

Is that likely to be a valid assumption or not?



I question whether it is required for residential. Call your local
electrical inspector and ask him. I have found that some electricians on
construction projects who have limited experience will just copy what
everyone else is doing and assume that is the correct way to go. None of
them read a code book.

  #4   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 91
Default crimped versus wirenutted grounds?


"John Grabowski" wrote in message
...

"jack" wrote in message
...
I replaced an outlet today at a commercial site. Now I admit I don't know
anything about commercial electrical, but around here grounds are required
to be crimped residentially; wirenutting isn't allowed.

I was surprised to see the ground was wirenutted. I assume that if
crimping is required for residential, it would also be required for
commercial.

Is that likely to be a valid assumption or not?



I question whether it is required for residential. Call your local
electrical inspector and ask him. I have found that some electricians on
construction projects who have limited experience will just copy what
everyone else is doing and assume that is the correct way to go. None of
them read a code book.

Well, the consensus seems to be that I am wrong; so maybe I will check on
it. Though I hate to have any more contact with the authorities than I have
to; when I applied for a building permit for a shed, the inspector wondered
why I never got a permit for my deck.

I learned it in a HS adult ed course taught by an electrical inspector. He
was perfectly clear that the only acceptable ground union was a crimp,
though he didn't know why.


  #5   Report Post  
Posted to alt.home.repair
Ken Ken is offline
external usenet poster
 
Posts: 40
Default crimped versus wirenutted grounds?


I learned it in a HS adult ed course taught by an electrical inspector. *He
was perfectly clear that the only acceptable ground union was a crimp,
though he didn't know why.-


If the only acceptable ground is a crimp, then why do they make
"greenies", the green wirenuts with a hole in the end for running one
of your grounds out the other end to attach to a device?

http://www.idealindustries.com/prodD...d=30-292&div=7

Ken


  #6   Report Post  
Posted to alt.home.repair
dpb dpb is offline
external usenet poster
 
Posts: 12,595
Default crimped versus wirenutted grounds?

Ken wrote:
....
If the only acceptable ground is a crimp, then why do they make
"greenies", the green wirenuts with a hole in the end for running one
of your grounds out the other end to attach to a device?


Because as at least one other has already said, _IF_ (the proverbial
"big if") it were true for the OP's jurisdiction it would be local code
restriction, not NEC...

--
  #7   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 929
Default crimped versus wirenutted grounds?

On Sep 24, 6:31*am, "jack" wrote:
"John Grabowski" wrote in message

...



"jack" wrote in message
...
I replaced an outlet today at a commercial site. *Now I admit I don't know
anything about commercial electrical, but around here grounds are required
to be crimped residentially; wirenutting isn't allowed.


I was surprised to see the ground was wirenutted. *I assume that if
crimping is required for residential, it would also be required for
commercial.


Is that likely to be a valid assumption or not?


I question whether it is required for residential. *Call your local
electrical inspector and ask him. *I have found that some electricians on
construction projects who have limited experience will just copy what
everyone else is doing and assume that is the correct way to go. *None of
them read a code book.


Well, the consensus seems to be that I am wrong; so maybe I will check on
it. *Though I hate to have any more contact with the authorities than I have
to; when I applied for a building permit for a shed, the inspector wondered
why I never got a permit for my deck.

I learned it in a HS adult ed course taught by an electrical inspector. *He
was perfectly clear that the only acceptable ground union was a crimp,
though he didn't know why.


Jack-

Perhaps your thought that "only acceptable ground union was a crimp"
is due to misinformation supplied by an electrical inspector who just
didn't know the real code requirements?

he did offer a not too reassuring comment that "he didn't know why"

cheers
Bob
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Accesibility of crimped/soldered cable joints? John Stumbles UK diy 3 July 17th 07 12:02 AM
Kero versus propane versus natural gas for heat Stormin Mormon Home Repair 1 October 27th 05 05:12 PM
coffee grounds? rick pixley Woodturning 35 August 16th 05 03:55 AM
Dadonator versus Forrest versus Freud -- comparisons Never Enough Money Woodworking 7 July 21st 05 07:45 PM
Heat pump versus oil versus propane in southern NH Gerome Home Ownership 3 October 7th 03 06:26 PM


All times are GMT +1. The time now is 08:37 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"