Default Observation port cover? ? ?

In August of 2007 our six-unit apartment building installed a Burnham V9A
series boiler (oil burning). The warranty was for one year.

When we had our spring inspection-servicing recently, we discovered that the
three-inch round glass lens on the rear, which the service manual calls the
Rear Observation Port Cover, was broken -- undoubtedly from the heat.

Our local service company says this part will cost $215 -- an astounding
amount for a small piece of glass.

My question is, do we really need this thing replaced?


  #2   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 561
Default Observation port cover? ? ?

On Apr 10, 5:59 pm, "Ray" wrote:
In August of 2007 our six-unit apartment building installed a Burnham V9A
series boiler (oil burning). The warranty was for one year.

When we had our spring inspection-servicing recently, we discovered that the
three-inch round glass lens on the rear, which the service manual calls the
Rear Observation Port Cover, was broken -- undoubtedly from the heat.

Our local service company says this part will cost $215 -- an astounding
amount for a small piece of glass.

My question is, do we really need this thing replaced?



If its allowing gasses to leak out, yes.

You may be able to replace it with a metal cover.


Dave
  #3   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 4,764
Default Observation port cover? ? ?

On Apr 10, 5:59 pm, "Ray" wrote:
In August of 2007 our six-unit apartment building installed a Burnham V9A
series boiler (oil burning). The warranty was for one year.

When we had our spring inspection-servicing recently, we discovered that the
three-inch round glass lens on the rear, which the service manual calls the
Rear Observation Port Cover, was broken -- undoubtedly from the heat.

Our local service company says this part will cost $215 -- an astounding
amount for a small piece of glass.

My question is, do we really need this thing replaced?


You're quoting a part price and the part is still under warranty, so
why should you have to pick up a material cost? Hopefully your
contract with the boiler installation company included a one year
parts and labor warranty. In some places that's the law, but you'd
have to check for your area.

Small condos and apartments have a knack for using one of the tenants
with barely any knowledge of construction to run the show, then when
there's a problem they find out that the contract was full of holes.
Hopefully that's not yours situation.

R
  #4   Report Post  
Posted to alt.home.repair
dpb dpb is offline
external usenet poster
 
Posts: 12,595
Default Observation port cover? ? ?

Ray wrote:
In August of 2007 our six-unit apartment building installed a Burnham V9A
series boiler (oil burning). The warranty was for one year.

When we had our spring inspection-servicing recently, we discovered that the
three-inch round glass lens on the rear, which the service manual calls the
Rear Observation Port Cover, was broken -- undoubtedly from the heat.

Our local service company says this part will cost $215 -- an astounding
amount for a small piece of glass.

My question is, do we really need this thing replaced?


Yes, it should be replaced. It's unusual for one to break on its
own--they're a refractory glass so temperature shouldn't be an issue
unless it wasn't mounted properly in the frame so could handle the
thermal expansion.

If the unit didn't go in until 08/2007, would seem the 1-year warranty
should be in effect.

--
  #5   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,934
Default Observation port cover? ? ?


"Ray" wrote in message
news:K4wLj.1028$PJ3.497@trndny02...
In August of 2007 our six-unit apartment building installed a Burnham V9A
series boiler (oil burning). The warranty was for one year.

When we had our spring inspection-servicing recently, we discovered that
the three-inch round glass lens on the rear, which the service manual
calls the Rear Observation Port Cover, was broken -- undoubtedly from the
heat.

Our local service company says this part will cost $215 -- an astounding
amount for a small piece of glass.

My question is, do we really need this thing replaced?



It sounds as though this is still under warranty so there should be no
charge for replacement. Call the manufacturer about the need for the part
and warranty satisfaction.



  #6   Report Post  
Posted to alt.home.repair
No Name
 
Posts: n/a
Default Observation port cover? ? ?

Sounds like it should be under warranty, unless they're claiming it was
broken by something not covered by the warranty.

That does sound expensive -- 3" dia x 1/8" thick extreme heat resistant
glass disc is under $50 at www.mcmaster.com

--
is Joshua Putnam
http://www.phred.org/~josh/
Braze your own bicycle frames. See
http://www.phred.org/~josh/build/build.html
  #7   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 5,823
Default Observation port cover? ? ?


"Ray" wrote in message
news:K4wLj.1028$PJ3.497@trndny02...
In August of 2007 our six-unit apartment building installed a Burnham V9A
series boiler (oil burning). The warranty was for one year.

When we had our spring inspection-servicing recently, we discovered that
the three-inch round glass lens on the rear, which the service manual
calls the Rear Observation Port Cover, was broken -- undoubtedly from the
heat.


I doubt it was from the heat. They are made to take heat, lots of it. The
ones on my boilers are 12, 14, and 25 years old.

It broke because it was either mishandled during installation of the boiler
or someone hit it with something.


Our local service company says this part will cost $215 -- an astounding
amount for a small piece of glass.

My question is, do we really need this thing replaced?


You can probably find it cheaper elsewhere. It may be covered under
warranty but that will have to be determined.


Yes, it must be replaced. Looking through the glass is one way of
determining if the boiler is firing properly, if ignition is taking place at
the right point, if the burner is sooting up. What scares me is that this
was not noticed until the spring inspection. Someone must be checking on
the boiler on a regular basis.

Rather than complain about the price of the part, you should be taking
someone to task for negligence. Boilers large enough to heat a six unit
building are in need of checking by a competent person that knows the signs
of trouble and they should look through that glass too. There should be a
checklist that is signed on a regular basis. Frankly, since you are asking
if it is ok to cheap out on the maintaining of a brand new boiler, you are
not the one to be in charge. It is an expensive piece of equipment and
should be cared for to protect your investment.

If you think $215 is expensive for a piece of glass, wait 'til you get the
cost of repairing parts that were not maintained.

Try here for your part
http://www.statesupply.com/displayCategory.do?Id=2120
Much cheaper


  #8   Report Post  
Posted to alt.home.repair
Ray Ray is offline
external usenet poster
 
Posts: 136
Default Observation port cover? ? ?

I didn't make myself clear -- the warranty expired a few weeks ago.


"RicodJour" wrote in message
...
On Apr 10, 5:59 pm, "Ray" wrote:
In August of 2007 our six-unit apartment building installed a Burnham V9A
series boiler (oil burning). The warranty was for one year.

When we had our spring inspection-servicing recently, we discovered that
the
three-inch round glass lens on the rear, which the service manual calls
the
Rear Observation Port Cover, was broken -- undoubtedly from the heat.

Our local service company says this part will cost $215 -- an astounding
amount for a small piece of glass.

My question is, do we really need this thing replaced?


You're quoting a part price and the part is still under warranty, so
why should you have to pick up a material cost? Hopefully your
contract with the boiler installation company included a one year
parts and labor warranty. In some places that's the law, but you'd
have to check for your area.

Small condos and apartments have a knack for using one of the tenants
with barely any knowledge of construction to run the show, then when
there's a problem they find out that the contract was full of holes.
Hopefully that's not yours situation.

R



  #9   Report Post  
Posted to alt.home.repair
Ray Ray is offline
external usenet poster
 
Posts: 136
Default Observation port cover? ? ?

I'll look at that site. Thanks.

wrote in message
.net...
Sounds like it should be under warranty, unless they're claiming it was
broken by something not covered by the warranty.

That does sound expensive -- 3" dia x 1/8" thick extreme heat resistant
glass disc is under $50 at www.mcmaster.com

--
is Joshua Putnam
http://www.phred.org/~josh/
Braze your own bicycle frames. See
http://www.phred.org/~josh/build/build.html



  #10   Report Post  
Posted to alt.home.repair
Ray Ray is offline
external usenet poster
 
Posts: 136
Default Observation port cover? ? ?

I'm sorry, I meant the installation was August of 2006.

"dpb" wrote in message ...
Ray wrote:
In August of 2007 our six-unit apartment building installed a Burnham V9A
series boiler (oil burning). The warranty was for one year.

When we had our spring inspection-servicing recently, we discovered that
the three-inch round glass lens on the rear, which the service manual
calls the Rear Observation Port Cover, was broken -- undoubtedly from the
heat.

Our local service company says this part will cost $215 -- an astounding
amount for a small piece of glass.

My question is, do we really need this thing replaced?


Yes, it should be replaced. It's unusual for one to break on its
own--they're a refractory glass so temperature shouldn't be an issue
unless it wasn't mounted properly in the frame so could handle the thermal
expansion.

If the unit didn't go in until 08/2007, would seem the 1-year warranty
should be in effect.

--



Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
OBSERVATION BEE HIVE J T Woodworking 4 September 21st 06 01:15 AM
I need circuit diagram of keyboard and mouse port, USB port, DDR port, IDE port,... fixpc Electronics Repair 6 March 1st 06 02:59 PM
3-port head on 2-port valve body??? Dark Angel UK diy 3 November 27th 05 03:45 PM
OBSERVATION HIVE J T Woodworking 0 August 17th 05 09:19 PM
2 port Vs 3 port central heating valves EMC UK diy 16 July 31st 03 08:09 PM


All times are GMT +1. The time now is 03:18 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"