[email protected] January 29th 08 05:01 AM

GFI for whirlpool tub
 
I am installing a whirlpool bathtub.The instructions say I have to
plug the pump into a 15a 110v seperate circuit protected with GFCI,
and the heater into a 15a 110v seperate circuit protected with gfci.I
take it I have to run wires to my main service box.I notice that gfci
circuit breakers are very expensive.Can I just install regular circuit
breakers and hook them up to gfci sockets by my bathtub.
Thanks

Tony Hwang January 29th 08 05:19 AM

GFI for whirlpool tub
 
wrote:
I am installing a whirlpool bathtub.The instructions say I have to
plug the pump into a 15a 110v seperate circuit protected with GFCI,
and the heater into a 15a 110v seperate circuit protected with gfci.I
take it I have to run wires to my main service box.I notice that gfci
circuit breakers are very expensive.Can I just install regular circuit
breakers and hook them up to gfci sockets by my bathtub.
Thanks


Hi,
There is a GFCI 15A circuit breker for that. Our tub is wired with it.
It is regular breaker like but with a tab which pops when there is
trouble in the circuit.

SteveB[_2_] January 29th 08 07:14 AM

GFI for whirlpool tub
 

wrote in message
...
I am installing a whirlpool bathtub.The instructions say I have to
plug the pump into a 15a 110v seperate circuit protected with GFCI,
and the heater into a 15a 110v seperate circuit protected with gfci.I
take it I have to run wires to my main service box.I notice that gfci
circuit breakers are very expensive.Can I just install regular circuit
breakers and hook them up to gfci sockets by my bathtub.
Thanks


Won't pass inspection, although you may not have it inspected if you DIY.
But it is an item that a house inspector would spot in a second if you go to
sell the house. And if there's ever a short without a GFI, the house may be
up for sale by the heirs.

Steve



hobbes January 29th 08 11:55 AM

GFI for whirlpool tub
 
On Jan 29, 2:14*am, "SteveB" wrote:
wrote in message

...

I am installing a whirlpool bathtub.The instructions say I have to
plug the pump into a 15a 110v seperate circuit protected with GFCI,
and the heater into a 15a 110v seperate circuit protected with gfci.I
take it I have to run wires to my main service box.I notice that gfci
circuit breakers are very expensive.Can I just install regular circuit
breakers and hook them up to gfci sockets by my bathtub.
Thanks


Won't pass inspection, although you may not have it inspected if you DIY.
But it is an item that a house inspector would spot in a second if you go to
sell the house. *And if there's ever a short without a GFI, the house may be
up for sale by the heirs.

Steve


Hi,

I think that what Mr. Trexxxmeis wanted to know is if he could use a
GFCI socket instead of a GFCI breaker because a GFCI breakers are
expensive.

I am not an expert in NEC code but I think that a GFCI breaker is
better in the respect that the GFCI's protection is outside the
bathroom away from water. Consider the following scenario. If water
from the bathtub were to get behing the GFCI socket which is in the
bathroom, this effectively eliminates the GFCI protection. The GFCI
breaker being in a different area of the house is of course not
exposed to this risk.

I suppose that GFCI socket could be used so long as that socket is
outside the bathroom and no water could get behind the GFCI. However
this now allows other appliances to be pluged into the same circuit as
the Whirlpool tub. This then breaks the "dedicated circuit rule." I
suppose you do not want to overload that 15 amp circuit for the
whirlpool heater.

Just my 2 cents.

best, Mike.

RBM[_2_] January 29th 08 12:10 PM

GFI for whirlpool tub
 
Yes you can. Run the two circuits to the location under the tub where the
support equipment is located and install a large deep two gang box with two
GFCI outlets in it , one for the pump and one for the heater





wrote in message
...
I am installing a whirlpool bathtub.The instructions say I have to
plug the pump into a 15a 110v seperate circuit protected with GFCI,
and the heater into a 15a 110v seperate circuit protected with gfci.I
take it I have to run wires to my main service box.I notice that gfci
circuit breakers are very expensive.Can I just install regular circuit
breakers and hook them up to gfci sockets by my bathtub.
Thanks




John Grabowski January 29th 08 12:40 PM

GFI for whirlpool tub
 

wrote in message
...
I am installing a whirlpool bathtub.The instructions say I have to
plug the pump into a 15a 110v seperate circuit protected with GFCI,
and the heater into a 15a 110v seperate circuit protected with gfci.I
take it I have to run wires to my main service box.I notice that gfci
circuit breakers are very expensive.Can I just install regular circuit
breakers and hook them up to gfci sockets by my bathtub.
Thanks


Usually a whirlpool bathtub requires a 20 amp circuit for each. You could
use the receptacles as ground fault protection but they would need to be
located away from the tub so that they could not be accessible by someone
standing in the tub. I don't know if this would pass inspection though as
the inspector might consider this a bathroom receptacle.

I usually use GFI switches for hydromassage bathtubs. They look like GFI
receptacles but do not have the openings to plug something in. The cost is
just a little more than a GFI receptacle. I prefer to locate them in a
linen closet in a bathroom or behind a door; a place where they are not
visually obvious, but readily accessible.


[email protected] January 29th 08 12:41 PM

GFI for whirlpool tub
 
On Jan 29, 7:10*am, "RBM" wrote:
Yes you can. Run the two circuits to the location under the tub where the
support equipment is located and install a large deep two gang box with two
GFCI outlets in it , one for the pump and one for the heater

wrote in message

...



I am installing a whirlpool bathtub.The instructions say I have to
plug the pump into a 15a 110v seperate circuit protected with GFCI,
and the heater into a 15a 110v seperate circuit protected with gfci.I
take it I have to run wires to my main service box.I notice that gfci
circuit breakers are very expensive.Can I just install regular circuit
breakers and hook them up to gfci sockets by my bathtub.
Thanks- Hide quoted text -


- Show quoted text -


Isn;t there something in the code that says permanently mounted
equipment can't be on a plug/cord/outlet arrangement? And doesn't
that apply here?

Twayne January 29th 08 04:22 PM

GFI for whirlpool tub
 
I am installing a whirlpool bathtub.The instructions say I have to
plug the pump into a 15a 110v seperate circuit protected with GFCI,
and the heater into a 15a 110v seperate circuit protected with gfci.I
take it I have to run wires to my main service box.I notice that gfci
circuit breakers are very expensive.Can I just install regular circuit
breakers and hook them up to gfci sockets by my bathtub.
Thanks


Yes, you can as long as local codes allow it.

--
Twayne

Tired of MS Office and their shananigans?
Try this free replacement:
http://www.openoffice.org



RBM[_2_] January 29th 08 10:07 PM

GFI for whirlpool tub
 
These units come with cords and plugs attached to them and are U.L.
approved. The outlets you install for them are located under the tub,
totally inaccessible without removing the access panel. Another approach is
what John Grabowski recommends, faceless GFCI's, but you still have to
install outlets under the tub, as that's how they're designed to be
connected



wrote in message
...
On Jan 29, 7:10 am, "RBM" wrote:
Yes you can. Run the two circuits to the location under the tub where the
support equipment is located and install a large deep two gang box with
two
GFCI outlets in it , one for the pump and one for the heater

wrote in message

...



I am installing a whirlpool bathtub.The instructions say I have to
plug the pump into a 15a 110v seperate circuit protected with GFCI,
and the heater into a 15a 110v seperate circuit protected with gfci.I
take it I have to run wires to my main service box.I notice that gfci
circuit breakers are very expensive.Can I just install regular circuit
breakers and hook them up to gfci sockets by my bathtub.
Thanks- Hide quoted text -


- Show quoted text -


Isn;t there something in the code that says permanently mounted
equipment can't be on a plug/cord/outlet arrangement? And doesn't
that apply here?