Default Power cable thickness q:

What kind of cable should I use to connect seven 50 W light. The cable draw power
from a 10A supply.

One thing I do not understand is that I have to use pretty thick wire but table
lamps have thin cables. What's the story here?
  #2   Report Post  
Posted to alt.home.repair
RBM RBM is offline
external usenet poster
 
Posts: 1,690
Default Power cable thickness q:

You have 350 watts. If you are operating a 120 volts, you've got less than 3
amps. The smallest recognized building conductor size is #14, which is good
for 15 amps




"John Smith" wrote in message
...
What kind of cable should I use to connect seven 50 W light. The cable
draw power
from a 10A supply.

One thing I do not understand is that I have to use pretty thick wire but
table
lamps have thin cables. What's the story here?



  #3   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 4,228
Default Power cable thickness q:


"John Smith" wrote in message
...
What kind of cable should I use to connect seven 50 W light. The cable
draw power
from a 10A supply.

One thing I do not understand is that I have to use pretty thick wire but
table
lamps have thin cables. What's the story here?


The size of the wire will depend on how far your lights are from the power
source.

In simple terms there are low voltage/high current circuits and high
voltage/low current circuits. The larger the current , the bigger the wire
will need to be to carry the same ammount of power. If the wire is not big
enough or too long for the size , the voltage will drop in the wire and the
light will not be as bright.

A 50 watt light operating on 120 volts will take about .4 amps and you can
run small wire a long distance. The same light operating on 12 volts will
about 4 amps. That is a 10 times differance so the wire will need to be
much larger.


  #4   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 4,500
Default Power cable thickness q:

On Nov 18, 8:29 am, John Smith wrote:
What kind of cable should I use to connect seven 50 W light. The cable draw power
from a 10A supply.

One thing I do not understand is that I have to use pretty thick wire but table
lamps have thin cables. What's the story here?


If this is a typical house wiring job, say to install some ceiling
lights in a dining room, then 14 gauge Romex is what would typically
be used. But it can also depend on the location and other details of
the install. Since this circuit is only 10amp, it must be fairly old
wiring.

The cable for 7 lights has to be a heavier gauge than the wire for one
table lamp because it must support the load of 7 lights, not just one.
  #5   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 696
Default Power cable thickness q:

On Sun, 18 Nov 2007 15:29:49 +0200, John Smith wrote
Re Power cable thickness q::

What kind of cable should I use to connect seven 50 W light. The cable draw power
from a 10A supply.

One thing I do not understand is that I have to use pretty thick wire but table
lamps have thin cables. What's the story here?


Use #14
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Broadband Cable & Mains Power Cable [email protected] UK diy 19 June 19th 07 10:20 AM
Electric shower/ Cable thickness Hake UK diy 5 November 3rd 06 07:28 AM
Power thickness planer choices Bob Moos Woodworking 24 May 28th 06 05:42 PM
Delta 12" Portable Thickness Planer or 22" Shop Built Thickness Sander? tillius Woodworking 11 December 21st 04 12:27 AM
Is MCB dependent on cable thickness.? Shabs UK diy 4 November 6th 04 11:55 AM


All times are GMT +1. The time now is 01:08 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"