Mikepier September 20th 07 04:34 PM

Cutting cast iron pipe w/o causing roof leak
 
I have to cut off a section of cast iron waste pipe in my attic to tie
in a vent .My concern is when I cut off the section of pipe, the
weight of the upper part of pipe would cause it to possible come
loose from the roof flashing and sink, thus causing a roof leak. The
last thing I want to do is open up a can of worms by doing this job. I
was wondering if I should be concerned or if anyone else has done a
job like this, what advice to offer. Thanks


Speedy Jim September 20th 07 04:44 PM

Cutting cast iron pipe w/o causing roof leak
 
Mikepier wrote:
I have to cut off a section of cast iron waste pipe in my attic to tie
in a vent .My concern is when I cut off the section of pipe, the
weight of the upper part of pipe would cause it to possible come
loose from the roof flashing and sink, thus causing a roof leak. The
last thing I want to do is open up a can of worms by doing this job. I
was wondering if I should be concerned or if anyone else has done a
job like this, what advice to offer. Thanks


I would fabricate a permanent support for the upper section.
Heavy steel strap clamp around it tied up to rafters.
If you put turnbuckles in the tie section you can preload it
before cutting.

If you can get on the roof to work, much better to simply
replace the section with PVC and a new rubber flashing boot.

Jim

JoeSpareBedroom September 20th 07 04:51 PM

Cutting cast iron pipe w/o causing roof leak
 
"Mikepier" wrote in message
ups.com...
I have to cut off a section of cast iron waste pipe in my attic to tie
in a vent .My concern is when I cut off the section of pipe, the
weight of the upper part of pipe would cause it to possible come
loose from the roof flashing and sink, thus causing a roof leak. The
last thing I want to do is open up a can of worms by doing this job. I
was wondering if I should be concerned or if anyone else has done a
job like this, what advice to offer. Thanks


I like Jim's idea, but I also think that even the slightest movement of the
pipe could affect the integrity of the seal around the flashing. You'd still
want to get up there with the appropriate caulk when the job's done.



franz frippl September 20th 07 05:02 PM

Cutting cast iron pipe w/o causing roof leak
 
On Thu, 20 Sep 2007 08:34:26 -0700, Mikepier wrote:

I have to cut off a section of cast iron waste pipe in my attic to tie
in a vent .My concern is when I cut off the section of pipe, the
weight of the upper part of pipe would cause it to possible come
loose from the roof flashing and sink, thus causing a roof leak. The
last thing I want to do is open up a can of worms by doing this job. I
was wondering if I should be concerned or if anyone else has done a
job like this, what advice to offer. Thanks




You didn't state exactly where you are working on the vent pipe. Chances
are you will see very little, if any, movement if you work below existing
vents tied into the main pipe. It would still be a wise choice to secure
the uppermost part of the pipe with strap supports designed to hold pipes
securely.

A reciprocating saw would seem to move the pipe less than doing so with a
handsaw.

I did exactly what you are doing several years back. That vent was cast
iron. I had to cut the pipe in the basement to reroute tub and stool.
There were enough pipes above me to support the vent without moving.

Reflashing or caulking the existing flash when done makes sense.

[email protected] September 20th 07 07:44 PM

Cutting cast iron pipe w/o causing roof leak
 
On Thu, 20 Sep 2007 16:02:54 GMT, franz frippl
wrote:

On Thu, 20 Sep 2007 08:34:26 -0700, Mikepier wrote:

I have to cut off a section of cast iron waste pipe in my attic to tie
in a vent .My concern is when I cut off the section of pipe, the
weight of the upper part of pipe would cause it to possible come
loose from the roof flashing and sink, thus causing a roof leak. The
last thing I want to do is open up a can of worms by doing this job. I
was wondering if I should be concerned or if anyone else has done a
job like this, what advice to offer. Thanks




You didn't state exactly where you are working on the vent pipe. Chances
are you will see very little, if any, movement if you work below existing
vents tied into the main pipe. It would still be a wise choice to secure
the uppermost part of the pipe with strap supports designed to hold pipes
securely.

A reciprocating saw would seem to move the pipe less than doing so with a
handsaw.

I did exactly what you are doing several years back. That vent was cast
iron. I had to cut the pipe in the basement to reroute tub and stool.
There were enough pipes above me to support the vent without moving.

Reflashing or caulking the existing flash when done makes sense.



If all you are doing is adding a vent, you can buy strap around
devices. Then cut a square hole in the cast pipe with an angle
grinder and attach the "strap on". You dont need to cut the whole
pipe. After all, it's only a vent.

Mikepier September 20th 07 08:01 PM

Cutting cast iron pipe w/o causing roof leak
 
On Sep 20, 2:44 pm, wrote:
On Thu, 20 Sep 2007 16:02:54 GMT, franz frippl
wrote:





On Thu, 20 Sep 2007 08:34:26 -0700, Mikepier wrote:


I have to cut off a section of cast iron waste pipe in my attic to tie
in a vent .My concern is when I cut off the section of pipe, the
weight of the upper part of pipe would cause it to possible come
loose from the roof flashing and sink, thus causing a roof leak. The
last thing I want to do is open up a can of worms by doing this job. I
was wondering if I should be concerned or if anyone else has done a
job like this, what advice to offer. Thanks


You didn't state exactly where you are working on the vent pipe. Chances
are you will see very little, if any, movement if you work below existing
vents tied into the main pipe. It would still be a wise choice to secure
the uppermost part of the pipe with strap supports designed to hold pipes
securely.


A reciprocating saw would seem to move the pipe less than doing so with a
handsaw.


I did exactly what you are doing several years back. That vent was cast
iron. I had to cut the pipe in the basement to reroute tub and stool.
There were enough pipes above me to support the vent without moving.


Reflashing or caulking the existing flash when done makes sense.


If all you are doing is adding a vent, you can buy strap around
devices. Then cut a square hole in the cast pipe with an angle
grinder and attach the "strap on". You dont need to cut the whole
pipe. After all, it's only a vent.- Hide quoted text -

- Show quoted text -


Is there a place online I can find out more about this?


JoeSpareBedroom September 20th 07 08:03 PM

Cutting cast iron pipe w/o causing roof leak
 
"Mikepier" wrote in message
ps.com...
On Sep 20, 2:44 pm, wrote:
On Thu, 20 Sep 2007 16:02:54 GMT, franz frippl
wrote:





On Thu, 20 Sep 2007 08:34:26 -0700, Mikepier wrote:


I have to cut off a section of cast iron waste pipe in my attic to tie
in a vent .My concern is when I cut off the section of pipe, the
weight of the upper part of pipe would cause it to possible come
loose from the roof flashing and sink, thus causing a roof leak. The
last thing I want to do is open up a can of worms by doing this job. I
was wondering if I should be concerned or if anyone else has done a
job like this, what advice to offer. Thanks


You didn't state exactly where you are working on the vent pipe.
Chances
are you will see very little, if any, movement if you work below
existing
vents tied into the main pipe. It would still be a wise choice to
secure
the uppermost part of the pipe with strap supports designed to hold
pipes
securely.


A reciprocating saw would seem to move the pipe less than doing so with
a
handsaw.


I did exactly what you are doing several years back. That vent was cast
iron. I had to cut the pipe in the basement to reroute tub and stool.
There were enough pipes above me to support the vent without moving.


Reflashing or caulking the existing flash when done makes sense.


If all you are doing is adding a vent, you can buy strap around
devices. Then cut a square hole in the cast pipe with an angle
grinder and attach the "strap on". You dont need to cut the whole
pipe. After all, it's only a vent.- Hide quoted text -

- Show quoted text -


Is there a place online I can find out more about this?


Open your yellow pages phone book and find a plumbing supply store. Go there
and ask.



Edwin Pawlowski September 20th 07 09:29 PM

Cutting cast iron pipe w/o causing roof leak
 

"JoeSpareBedroom" wrote in message

Open your yellow pages phone book and find a plumbing supply store. Go
there and ask.


Oh man, that requires interacting with real people.



JoeSpareBedroom September 20th 07 09:30 PM

Cutting cast iron pipe w/o causing roof leak
 
"Edwin Pawlowski" wrote in message
news:oKAIi.3456$yO2.2867@trndny01...

"JoeSpareBedroom" wrote in message

Open your yellow pages phone book and find a plumbing supply store. Go
there and ask.


Oh man, that requires interacting with real people.



I'm gettin' a headache just thinking about it.



Wayne Whitney September 20th 07 10:50 PM

Cutting cast iron pipe w/o causing roof leak
 
On 2007-09-20, Speedy Jim wrote:

If you can get on the roof to work, much better to simply
replace the section with PVC and a new rubber flashing boot.


DWV PVC as roof vent requires painting, as the material is not made
with UV inhibitors?

Cheers, Wayne

[email protected] September 21st 07 11:12 AM

Cutting cast iron pipe w/o causing roof leak
 
On Thu, 20 Sep 2007 12:01:11 -0700, Mikepier
wrote:

On Sep 20, 2:44 pm, wrote:
On Thu, 20 Sep 2007 16:02:54 GMT, franz frippl
wrote:





On Thu, 20 Sep 2007 08:34:26 -0700, Mikepier wrote:


I have to cut off a section of cast iron waste pipe in my attic to tie
in a vent .My concern is when I cut off the section of pipe, the
weight of the upper part of pipe would cause it to possible come
loose from the roof flashing and sink, thus causing a roof leak. The
last thing I want to do is open up a can of worms by doing this job. I
was wondering if I should be concerned or if anyone else has done a
job like this, what advice to offer. Thanks


You didn't state exactly where you are working on the vent pipe. Chances
are you will see very little, if any, movement if you work below existing
vents tied into the main pipe. It would still be a wise choice to secure
the uppermost part of the pipe with strap supports designed to hold pipes
securely.


A reciprocating saw would seem to move the pipe less than doing so with a
handsaw.


I did exactly what you are doing several years back. That vent was cast
iron. I had to cut the pipe in the basement to reroute tub and stool.
There were enough pipes above me to support the vent without moving.


Reflashing or caulking the existing flash when done makes sense.


If all you are doing is adding a vent, you can buy strap around
devices. Then cut a square hole in the cast pipe with an angle
grinder and attach the "strap on". You dont need to cut the whole
pipe. After all, it's only a vent.- Hide quoted text -

- Show quoted text -


Is there a place online I can find out more about this?


Possibly..... There are some plumbing supply stores online. However,
I'd check your local plumbing supply places. These things are
commonly used. I dont know the exact name for them, but I have seen
them. It's basically just a device that fits around the cast iron
pipe. It fits around about half the pipe, has a rubber gasket, and
uses large hose clamps to attach it. There will be a 1.5 or 2 inch
threaded hole in the side to attach your pipe. They also make similar
devices for water pipes, so it's easier to attach a water source to an
ice maker. Those are called "saddle valves", but they have an actual
valve built in. Knowing that, these drain pipe devices could be
called "saddle" (something). Just a guess.

willshak September 21st 07 12:42 PM

Cutting cast iron pipe w/o causing roof leak
 
on 9/20/2007 4:29 PM Edwin Pawlowski said the following:
"JoeSpareBedroom" wrote in message

Open your yellow pages phone book and find a plumbing supply store. Go
there and ask.



Oh man, that requires interacting with real people.


I hate real people.Cyber people are better.

--

Bill