Default Attic roof vent and ventilation

I was thinking of installing some sort of roof vent directly over my
unfinished attic to vent out some of the heat and moisture in summer.
I live in NY. My house was originally a ranch and then the original owner
had a second story put on the house (40 years ago). From what I can tell by
living here for the past 15 years the upstairs level was not constructed
very well with regards to energy efficiency and/or insulation. There does
not seem to be any soffit vents, other than the few small ones I added
myself in the past few years. The attic, which I can walk into as the
previous owner put plywood down, has a small double-hung window at one end
which I always leave open for ventilation. Above this window is the small
typical louvered aluminum vent.

Two years ago I had a new roof (asphalt shingles) put on. There was a fair
amount of water damage to the underlying exterior plywood which the roofers
replaced as they went along. I have no doubt that part of the damage was
caused by poor/no ventilation.

I should also note that the previous owner, for some reason although the
attic is not finished, placed foil-faced insulation under all the roofing in
the attic. Not sure why he did this and I also think that this is not a
good idea in winter as it probably traps moisture right at the roof wood. I
have seen some frosty areas on the attic roof wood on occasion.

In summer the upstairs living areas get really hot. I do have central a/c
up there but it cannot keep pace with the afternoon heat of the sun and does
not cool the upstairs until after the sun goes down. This leads me to
believe that there is little, if any, remaining insulation under the roof
but above the living areas.

I was originally thinking of installing a powered roof vent but I hear that
sometimes the pressure from the vented air can suck air conditioned air from
surrounding rooms and out the roof. So now I'm not sure about doing this.
Perhaps installing some non-powered roof vents or a turbine would help but
without soffit vents to allow air in under the eaves it would probably not
help much.

I want to get a qualified energy audit person/company in to my house for
additional ideas.
Any thoughts on all this?

Thanks,
Walter


  #2   Report Post  
Posted to misc.consumers.house,alt.home.repair
external usenet poster
 
Posts: 4,500
Default Attic roof vent and ventilation


Walter Cohen wrote:
I was thinking of installing some sort of roof vent directly over my
unfinished attic to vent out some of the heat and moisture in summer.
I live in NY. My house was originally a ranch and then the original owner
had a second story put on the house (40 years ago). From what I can tell by
living here for the past 15 years the upstairs level was not constructed
very well with regards to energy efficiency and/or insulation. There does
not seem to be any soffit vents, other than the few small ones I added
myself in the past few years. The attic, which I can walk into as the
previous owner put plywood down, has a small double-hung window at one end
which I always leave open for ventilation. Above this window is the small
typical louvered aluminum vent.

Two years ago I had a new roof (asphalt shingles) put on. There was a fair
amount of water damage to the underlying exterior plywood which the roofers
replaced as they went along. I have no doubt that part of the damage was
caused by poor/no ventilation.

I should also note that the previous owner, for some reason although the
attic is not finished, placed foil-faced insulation under all the roofing in
the attic. Not sure why he did this and I also think that this is not a
good idea in winter as it probably traps moisture right at the roof wood. I
have seen some frosty areas on the attic roof wood on occasion.

In summer the upstairs living areas get really hot. I do have central a/c
up there but it cannot keep pace with the afternoon heat of the sun and does
not cool the upstairs until after the sun goes down. This leads me to
believe that there is little, if any, remaining insulation under the roof
but above the living areas.

I was originally thinking of installing a powered roof vent but I hear that
sometimes the pressure from the vented air can suck air conditioned air from
surrounding rooms and out the roof. So now I'm not sure about doing this.
Perhaps installing some non-powered roof vents or a turbine would help but
without soffit vents to allow air in under the eaves it would probably not
help much.

I want to get a qualified energy audit person/company in to my house for
additional ideas.
Any thoughts on all this?

Thanks,
Walter



I'd get a lot more soffitting venting in place, preferably a continuous
one. Then, I'd probably go with a ridge vent, which doesn't require
any power and provides uniform air flow, as opposed to a point which is
what you get with a gable, turbine, power fan, etc.

As to the foil faced insulation on the rafters, is it actual insulation
or a radiant barrier, which is just an aluminum shield? If it has
insulation, how much air space is open between the insulation and the
roof? Is there a clear channel from soffit to peak and a way for the
air to get in and out?

  #3   Report Post  
Posted to misc.consumers.house,alt.home.repair
external usenet poster
 
Posts: 479
Default Attic roof vent and ventilation

Walter Cohen wrote:
I was thinking of installing some sort of roof vent directly over my
unfinished attic to vent out some of the heat and moisture in summer.
I live in NY. My house was originally a ranch and then the original
owner had a second story put on the house (40 years ago). From what
I can tell by living here for the past 15 years the upstairs level
was not constructed very well with regards to energy efficiency
and/or insulation. There does not seem to be any soffit vents, other
than the few small ones I added myself in the past few years. The
attic, which I can walk into as the previous owner put plywood down,
has a small double-hung window at one end which I always leave open
for ventilation. Above this window is the small typical louvered
aluminum vent.
Two years ago I had a new roof (asphalt shingles) put on. There was
a fair amount of water damage to the underlying exterior plywood
which the roofers replaced as they went along. I have no doubt that
part of the damage was caused by poor/no ventilation.

I should also note that the previous owner, for some reason although
the attic is not finished, placed foil-faced insulation under all the
roofing in the attic. Not sure why he did this and I also think that
this is not a good idea in winter as it probably traps moisture right
at the roof wood. I have seen some frosty areas on the attic roof
wood on occasion.
In summer the upstairs living areas get really hot. I do have
central a/c up there but it cannot keep pace with the afternoon heat
of the sun and does not cool the upstairs until after the sun goes
down. This leads me to believe that there is little, if any,
remaining insulation under the roof but above the living areas.

I was originally thinking of installing a powered roof vent but I
hear that sometimes the pressure from the vented air can suck air
conditioned air from surrounding rooms and out the roof. So now I'm
not sure about doing this. Perhaps installing some non-powered roof
vents or a turbine would help but without soffit vents to allow air
in under the eaves it would probably not help much.

I want to get a qualified energy audit person/company in to my house
for additional ideas.
Any thoughts on all this?

Thanks,
Walter


I agree with what trader wrote and was asking about.

You need to get air flow. Having just a outlet does not help, you need
to have inlets as well. Usually the best inlets are low at the soffits.
The exhaust vents should be high at the ridge. The difference in air
temperature will move the air and the hotter it is the more air it will
move.

I would avoid any kind of powered vents due to noise, maintenance and
cost.

--
Joseph Meehan

Dia duit


  #4   Report Post  
Posted to misc.consumers.house,alt.home.repair
external usenet poster
 
Posts: 121
Default Attic roof vent and ventilation

Actually, when I had new roofing shingles put on I paid for and had them add
a ridge vent the length of the roof. I have no idea if they put it on/in
correctly as I understand they would need to cut out a portion of the very
top wood along the ridge line for the length of the roof. Is there any way
to tell from inside/outside? Still, even with a ridge vent there is no (or
very few) soffit vents.

Who would put these soffit vents in - roofer or general contractor?

Thanks,
Walter

wrote in message
ups.com...

Walter Cohen wrote:
I was thinking of installing some sort of roof vent directly over my
unfinished attic to vent out some of the heat and moisture in summer.
I live in NY. My house was originally a ranch and then the original
owner
had a second story put on the house (40 years ago). From what I can tell
by
living here for the past 15 years the upstairs level was not constructed
very well with regards to energy efficiency and/or insulation. There
does
not seem to be any soffit vents, other than the few small ones I added
myself in the past few years. The attic, which I can walk into as the
previous owner put plywood down, has a small double-hung window at one
end
which I always leave open for ventilation. Above this window is the
small
typical louvered aluminum vent.

Two years ago I had a new roof (asphalt shingles) put on. There was a
fair
amount of water damage to the underlying exterior plywood which the
roofers
replaced as they went along. I have no doubt that part of the damage was
caused by poor/no ventilation.

I should also note that the previous owner, for some reason although the
attic is not finished, placed foil-faced insulation under all the roofing
in
the attic. Not sure why he did this and I also think that this is not a
good idea in winter as it probably traps moisture right at the roof wood.
I
have seen some frosty areas on the attic roof wood on occasion.

In summer the upstairs living areas get really hot. I do have central
a/c
up there but it cannot keep pace with the afternoon heat of the sun and
does
not cool the upstairs until after the sun goes down. This leads me to
believe that there is little, if any, remaining insulation under the roof
but above the living areas.

I was originally thinking of installing a powered roof vent but I hear
that
sometimes the pressure from the vented air can suck air conditioned air
from
surrounding rooms and out the roof. So now I'm not sure about doing
this.
Perhaps installing some non-powered roof vents or a turbine would help
but
without soffit vents to allow air in under the eaves it would probably
not
help much.

I want to get a qualified energy audit person/company in to my house for
additional ideas.
Any thoughts on all this?

Thanks,
Walter



I'd get a lot more soffitting venting in place, preferably a continuous
one. Then, I'd probably go with a ridge vent, which doesn't require
any power and provides uniform air flow, as opposed to a point which is
what you get with a gable, turbine, power fan, etc.

As to the foil faced insulation on the rafters, is it actual insulation
or a radiant barrier, which is just an aluminum shield? If it has
insulation, how much air space is open between the insulation and the
roof? Is there a clear channel from soffit to peak and a way for the
air to get in and out?



  #5   Report Post  
Posted to misc.consumers.house,alt.home.repair
Sev Sev is offline
external usenet poster
 
Posts: 160
Default Attic roof vent and ventilation


Along with what Joseph and Trader said, I would check/ improve
insulation between living area and attic. If I'm understanding
correctly, attic is above 2nd floor living area, not unfinished portion
of same. Since you mention decking is in place, you would either have
to pull it up or have insulation, such as cellulose, blown in.



  #6   Report Post  
Posted to misc.consumers.house,alt.home.repair
external usenet poster
 
Posts: 4,500
Default Attic roof vent and ventilation


Walter Cohen wrote:
Actually, when I had new roofing shingles put on I paid for and had them add
a ridge vent the length of the roof. I have no idea if they put it on/in
correctly as I understand they would need to cut out a portion of the very
top wood along the ridge line for the length of the roof. Is there any way
to tell from inside/outside? Still, even with a ridge vent there is no (or
very few) soffit vents.

Who would put these soffit vents in - roofer or general contractor?

Thanks,
Walter


A general contractor should be fine. Or a roofer. You can even do it
yourself, depending on how high they are and how easy to get to.
Basicly you need to run a saw down the length of the house twice, set
to a depth to just cut off the soffit material creating a channel the
vent goes in.

You can see if you have a ridge vent by going in the attic. At the
peak, there should be a piece of sheathing gone, about 2" on each side.
And it should be covered by the ridge vent, the underside of which
will be visible.

There are a wide range of ridge vents and I think considerable diff in
how much air flow they allow, as some are more like foam filter
material, others are more open.





wrote in message
ups.com...

Walter Cohen wrote:
I was thinking of installing some sort of roof vent directly over my
unfinished attic to vent out some of the heat and moisture in summer.
I live in NY. My house was originally a ranch and then the original
owner
had a second story put on the house (40 years ago). From what I can tell
by
living here for the past 15 years the upstairs level was not constructed
very well with regards to energy efficiency and/or insulation. There
does
not seem to be any soffit vents, other than the few small ones I added
myself in the past few years. The attic, which I can walk into as the
previous owner put plywood down, has a small double-hung window at one
end
which I always leave open for ventilation. Above this window is the
small
typical louvered aluminum vent.

Two years ago I had a new roof (asphalt shingles) put on. There was a
fair
amount of water damage to the underlying exterior plywood which the
roofers
replaced as they went along. I have no doubt that part of the damage was
caused by poor/no ventilation.

I should also note that the previous owner, for some reason although the
attic is not finished, placed foil-faced insulation under all the roofing
in
the attic. Not sure why he did this and I also think that this is not a
good idea in winter as it probably traps moisture right at the roof wood.
I
have seen some frosty areas on the attic roof wood on occasion.

In summer the upstairs living areas get really hot. I do have central
a/c
up there but it cannot keep pace with the afternoon heat of the sun and
does
not cool the upstairs until after the sun goes down. This leads me to
believe that there is little, if any, remaining insulation under the roof
but above the living areas.

I was originally thinking of installing a powered roof vent but I hear
that
sometimes the pressure from the vented air can suck air conditioned air
from
surrounding rooms and out the roof. So now I'm not sure about doing
this.
Perhaps installing some non-powered roof vents or a turbine would help
but
without soffit vents to allow air in under the eaves it would probably
not
help much.

I want to get a qualified energy audit person/company in to my house for
additional ideas.
Any thoughts on all this?

Thanks,
Walter



I'd get a lot more soffitting venting in place, preferably a continuous
one. Then, I'd probably go with a ridge vent, which doesn't require
any power and provides uniform air flow, as opposed to a point which is
what you get with a gable, turbine, power fan, etc.

As to the foil faced insulation on the rafters, is it actual insulation
or a radiant barrier, which is just an aluminum shield? If it has
insulation, how much air space is open between the insulation and the
roof? Is there a clear channel from soffit to peak and a way for the
air to get in and out?


Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Question on attic ventilation Doug Steckel Home Repair 18 June 1st 06 05:49 AM
roof vent, ridge vent or what? [email protected] Home Repair 11 May 19th 06 06:06 AM
gable vent (bats!) - Attic ventilation Rich Home Repair 9 December 15th 04 05:16 PM
Get a New Roof But Don't Add Any Ventilation? Jay Chan Home Repair 12 March 30th 04 06:16 PM
Attic Ventilation Expert Needed - North NJ Area jeff Home Repair 11 March 12th 04 11:35 AM


All times are GMT +1. The time now is 04:58 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"