Hi March 9th 06 07:02 PM

Carrier Humidifier problem
 
I have a Carrier model 58WAV136-16 furnace. It has a humidifier attachment,
and it seems that it is not sending any power to the solenoid that turns it
on.

Does anyone know what conditions have to exist (that I haven't thought of)
to flip the humidifier on? Things that I have thought of:

1. The fan has to be going
2. The humidistat needs to be set high enough to trip

Anything else? I opened the panel and checked the DC output of the
humidifier port and there is nothing coming out of it.

Any ideas?

Thanks



Dr. Hardcrab March 9th 06 09:23 PM

Carrier Humidifier problem
 

"Hi" wrote in message
news:rZ_Pf.235295$oG.168140@dukeread02...
I have a Carrier model 58WAV136-16 furnace. It has a humidifier
attachment, and it seems that it is not sending any power to the solenoid
that turns it on.

Does anyone know what conditions have to exist (that I haven't thought of)
to flip the humidifier on? Things that I have thought of:

1. The fan has to be going
2. The humidistat needs to be set high enough to trip

Anything else? I opened the panel and checked the DC output of the
humidifier port and there is nothing coming out of it.

Any ideas?


How does it know the fan is running? In other words, could it be using a
current sensing relay that has gone bad?



[email protected] March 9th 06 10:30 PM

Carrier Humidifier problem
 
Also, some can be wired so that they go on when the furnace burner is
activated, instead of the blower. That's how mine is set up, which I
think has the advantage that after the burner shuts off, the humidifier
does too, so the remaing few minutes of blower time can dry out the
media. Plus I don't have to worry about turning it off during cooling
season.


Dr. Hardcrab March 9th 06 11:31 PM

Carrier Humidifier problem
 

wrote in message
oups.com...
Also, some can be wired so that they go on when the furnace burner is
activated, instead of the blower. That's how mine is set up, which I
think has the advantage that after the burner shuts off, the humidifier
does too, so the remaing few minutes of blower time can dry out the
media. Plus I don't have to worry about turning it off during cooling
season.


Damn! Nice idea. Never seen it done that way, but it makes sense!



Dr. Hardcrab March 10th 06 02:11 AM

Carrier Humidifier problem
 

"Bubba " ReMoVe wrote in message
...
On Thu, 09 Mar 2006 23:31:37 GMT, "Dr. Hardcrab"
wrote:


wrote in message
groups.com...
Also, some can be wired so that they go on when the furnace burner is
activated, instead of the blower. That's how mine is set up, which I
think has the advantage that after the burner shuts off, the humidifier
does too, so the remaing few minutes of blower time can dry out the
media. Plus I don't have to worry about turning it off during cooling
season.


Damn! Nice idea. Never seen it done that way, but it makes sense!


Thats how most of them work nowadays. Thats what the H or HUM terminal
is for on most furnace circuit boards.
Bubba


Yeah. The terminals have been around for a while but I thought it just
brought the humidifier on with the fan.