dumb hot air furnace question
Is the fan before or after the heat exchanger? I.e. is the heat
exchanger under positive or negative pressure? Thanks, Pondering |
dumb hot air furnace question
"z" wrote in message oups.com... Is the fan before or after the heat exchanger? I.e. is the heat exchanger under positive or negative pressure? Thanks, Pondering positive pressure usually |
dumb hot air furnace question
Everyone I've ever seen the blower is before the heat exchanger, which
only makes sense, as you wouldn't want to put a motor in a hot area if you can help it. |
dumb hot air furnace question
"z" wrote in message oups.com... Is the fan before or after the heat exchanger? I.e. is the heat exchanger under positive or negative pressure? Thanks, Pondering The air path in the hot air furnances that I've had is: cold/return air--filter--blower--heat exchanger--plenum--humidifier--supply pipes. So, if anything, there is a slight positive pressure in the area around the heat exchanger relative to room air. TKM |
dumb hot air furnace question
yes the blower is before the heat exchanger
also so that the heat exchanger is under positive pressure... if the heat exchanger cracks the distribution air will be forced into the combustion air and not the other way rond which would be much more dangerous... http://www.bacharach-training.com/Tips/Tips.htm Mark |
dumb hot air furnace question
On 20 Dec 2005 12:50:32 -0800, "z" wrote:
Is the fan before or after the heat exchanger? I.e. is the heat exchanger under positive or negative pressure? Thanks, Pondering Mine's a big-ass squirrel-cage that forces air TO the heat-exchanger, presumably also because on the other side all the parts would have to stand up to more heat. |
dumb hot air furnace question
On 20 Dec 2005 12:50:32 -0800, "z" wrote:
Is the fan before or after the heat exchanger? I.e. is the heat exchanger under positive or negative pressure? Thanks, Pondering I don't think that is a dumb question, and the answers were interesting. And remember, there is no such thing as a dumb question. Only a dumb person. Remove NOPSAM to email me. Please let me know if you have posted also. |
dumb hot air furnace question
"mm" wrote in message And remember, there is no such thing as a dumb question. Only a dumb person. What if they start asking questions though? |
dumb hot air furnace question
Edwin Pawlowski wrote: "mm" wrote in message And remember, there is no such thing as a dumb question. Only a dumb person. What if they start asking questions though? Case rested :) hvacrmedic |
dumb hot air furnace question
Mark wrote: yes the blower is before the heat exchanger also so that the heat exchanger is under positive pressure... if the heat exchanger cracks the distribution air will be forced into the combustion air and not the other way rond which would be much more dangerous... http://www.bacharach-training.com/Tips/Tips.htm Mark Yeah, that was kind of my hunch. There was a puddle of oil in the bottom under the burner, and I was thinking the air leaking from the exchanger maybe blew it away from the burner. |
dumb hot air furnace question
Edwin Pawlowski wrote:
"mm" wrote in message And remember, there is no such thing as a dumb question. Only a dumb person. What if they start asking questions though? Then you have "dumb person questions," which is really what is commonly meant by a "dumb question." |
dumb hot air furnace question
On Wed, 21 Dec 2005 03:21:56 GMT, "Edwin Pawlowski"
wrote: "mm" wrote in message And remember, there is no such thing as a dumb question. Only a dumb person. What if they start asking questions though? Darn. LOL Remove NOPSAM to email me. Please let me know if you have posted also. |
dumb hot air furnace question
On Tue, 20 Dec 2005 20:57:07 -0500, mm
wrote: On 20 Dec 2005 12:50:32 -0800, "z" wrote: Is the fan before or after the heat exchanger? I.e. is the heat exchanger under positive or negative pressure? Thanks, Pondering I don't think that is a dumb question, and the answers were interesting. And remember, there is no such thing as a dumb question. Only a dumb person. FTR, I left off the smiley but I was kidding. I had a girlfriend for a while, and one of her big complaints was that I asked questions, the answers to which were obvious. I hadn't noticed this, but I spent years paying attention, and it was true. But it was still a good idea. I usually got more information in return than I already knew. Sometimes what I thought was the answer wasn't. And people don't like it when you start off with a really hard question. But if I ask an easy question first, and he answers it and I appreciate the answer and show it, we're both happy. If I have another question, he'll make a bigger effort to answer it. This happens with me especially if I'm just watching someone working in public, who has no responsibility to answer my questions at all. Remove NOPSAM to email me. Please let me know if you have posted also. Remove NOPSAM to email me. Please let me know if you have posted also. |