On 14 Jun 2005 12:07:53 -0700, "Too_Many_Tools"
wrote:

When one considers a workshop with metal and wood working capabilities,
what tradeoffs have you made to have a working shop in an alternate
homepower environment where every amp is precious?


8kW (surges to 16) can handle most everything a home shop is likely to
have. We have a few limitations - Hypertherm 600 suffers nuisance
cut-outs above 45 Amps. It will also temporarily shut down if the
compressor starts mid-cut. So I let the compressor tank fill, then
shut the pump power off before starting the cut. For prolonged cutting
at max output, I run the backup generator for boost. Lincoln SW TIG
175 can't be run at full output off our inverters, amp draw is too
high. Could be solved by trading up to an inverter based unit if I
didn't already have an engine driven substitute for the bigger jobs.
Powermig 255 seems perfectly happy at full output.

Obviously hand nonpowered tools take on a special importance.


Yuck! Perish the thought.

Cordless tools come to mind but which ones and what batteries?


Cordless tools are great for jobs where the cord is a nuisance, but
there' isn't any special need for them with home power. Careful though
if you're using some of the modsquare (often called modsine)
inverters, they can cook the chargers included with some cordless
tools.

When considerng stationary tools like drills, lathes, mills, saws,
grinders, etc., which ones fit best in an environment where one is off
grid?


There aren't really any special considerations unless you're trying to
get away with too-small inverter capacity. Keep in mind that if you're
maxing out system capacity in the shop, it won't be available in the
house at the same time. Having said that, I don't bother to tell my
wife what I'm up to in the shop. If together we managed to exceed
capacity, the inverters would trip off automatically. And that could
happen more easily if for instance batteries were low, and you have
surges due to large loads starting. The temporary voltage drop might
be sensed, and cause a shutdown.

Special operations like welding and using air compressors would seem to
need consideration because of their unique requirements.


One thing I've done with all equipment purchases is to make sure
they're easily returnable just in case they're not compatible with the
inverters. VFDs could be an issue for instance. Although the only
thing we've ever returned due to incompatibility was a bread maker
that ran at double speed.

Wayne