Mathew Newton wrote :
For a 2.5mm2 radial circuit supplying a washing machine (via a double 13A
socket) and a boiler/pump/valves (via 3A FCU) would a 16A or 20A MCB be
'best', and why?


Radial circuit in 2.5mm you can use a 20amp MCB.