View Single Post
  #1   Report Post  
Posted to uk.d-i-y
ernie mendoza ernie mendoza is offline
external usenet poster
 
Posts: 5
Default New boiler undergassed. Blame gas meter governor?

I have just had a new Worcester-Bosch 24i system boiler installed in
the loft to replace a 30-year-old non-condensing boiler in the
kitchen. Tests show it is "undergassed". The installer says it may
be a problem with the gas meter governor, in which case they say
Transco would have to fix it. However the 22mm pipe required by the
boiler is connected to a 15mm pipe from the gas meter. Should the
installer fit a larger pipe to the gas meter instead of blaming the
governor and shifting the problem to Transco? Any advice most
welcome.